{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25F47E250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25F47E250","canonicalUrl":"https://aoctrl.com/schneider/C25F47E250","factsUrl":"https://aoctrl.com/api/mcp/products/C25F47E250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX250F, 250 A, 85 kA Icu at 240 V AC, 4P, MicroLogic 7.2 E trip unit, EN/IEC 60947-2.","salesMarkdown":"The C25F47E250 is a Schneider Electric ComPacT NSX250F molded case circuit breaker, 4-pole, rated 250 A at 40 °C with a MicroLogic 7.2 E electronic trip unit. At 415 V AC the breaking capacity is 36 kA Icu, still enough for most distribution boards in European industrial plants. The trip unit covers L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection — one device handles both overcurrent and ground-fault, so no separate RCD needed downstream. The LCD display on the front gives you real-time metering and alarm readouts without opening the door. ## Mounting and integration — checklist for the panel builder Front connections top and bottom, 35 mm connection pitch. Neutral on the left. The 161 mm height by 140 mm width by 86 mm depth fits standard MCCB cutouts; verify the backplate clearance for the toggle handle and LCD.","metaTitle":"Schneider Electric C25F47E250 ComPacT NSX250F, 250 A, 85 kA","metaDescription":"Schneider Electric C25F47E250 ComPacT NSX250F molded case circuit breaker, 250 A, 85 kA Icu at 240 V AC, MicroLogic 7.2 E trip unit. Active production, sourced to order. Request qu","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,784.39 – $5,157.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4184cdb78d2a84f99e4ab61481fa9bfa.pdf","sourceUrl":"https://www.se.com/ng/en/product/C25F47E250/circuit-breaker-compact-nsx250f-36ka-415vac-4-poles-micrologic-vigi-7-2e-trip-unit-250a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25F47E250/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25F47E250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25F47E250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}