{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25H34V100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25H34V100","canonicalUrl":"https://aoctrl.com/schneider/C25H34V100","factsUrl":"https://aoctrl.com/api/mcp/products/C25H34V100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, C25H34V100, 3P earth leakage circuit breaker, 100 A at 40 °C, MicroLogic 4.2 trip unit, 70 kA Icu at 415 V AC.","salesMarkdown":"It combines overload (L), short-time short-circuit (So), instantaneous short-circuit (I), and integrated earth-leakage (R) protection in one device — so a single unit handles both overcurrent and ground-fault duties on a distribution feeder. Rated 100 A at 40 °C, it carries a breaking capacity of 70 kA Icu at 415 V AC (per IEC 60947-2) and 65 kA Icu at 480 V AC (per UL 60947-4-1). That 70 kA at 415 V puts it in the H breaking-capacity class — enough for most industrial main or sub-main switchboards where fault currents run high. If your panel runs hotter, you derate — the electronic MicroLogic 4.2 includes a thermal-memory function that tracks 20 minutes of heating before and after a trip, so it won't reclose into a still-hot load. Breaking capacity varies by voltage: 100 kA at 240 V, 70 kA at 415 V, 65 kA at 440 V, down to 10 kA at 690 V. For a 480 V panel, the 65 kA Icu per UL 60947-4-1 is the number to coordinate with upstream gear. The breaker is Category A — no intentional short-time delay, so it trips fast on a hard fault, which simplifies selective coordination with downstream devices but means you need a higher-rated upstream breaker if you want zone selectivity. Integrated earth-leakage protection means the MicroLogic 4.2 senses residual current directly — no add-on module or external RCD. The OFF position uses a rotary switch marked IΔn for setting the leakage threshold. That saves panel space and wiring vs. a separate ground-fault relay. Front connections top and bottom with a 35 mm connection pitch — standard for panel-board busbar or cable lugging. IP40 enclosure protection and IK07 impact resistance suit it for indoor switchgear; not rated for washdown.","metaTitle":"Schneider Electric C25H34V100 ComPacT NSX 100 A Earth Leakag","metaDescription":"Schneider Electric C25H34V100 ComPacT NSX 100 A earth leakage circuit breaker, 3P, MicroLogic 4.2, 70 kA at 415 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Operating mode":"OFF using the IΔn rotary switch","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection R : for earth-leakage protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX250H","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"H 70 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"25 W N 25 W L1 and L3 20.6 W L2","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable","[Ir] long-time protection pick-up adjustment range":"40...100 A","[Δt] residual earth-leakage time delay adjustment":"0 ms 60 ms 150 ms 500 ms 1 s","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,245.13 – $2,839.32","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/02ebc43d10252264ae8dc71f27d93f49.pdf","sourceUrl":"https://www.se.com/vn/en/product/C25H34V100/circuit-breaker-compact-nsx250h-70ka-415vac-3-poles-micrologic-vigi-4-2-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25H34V100/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C25H34V100 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is C25H34V100's listed range on this component line?","answer":"It belongs to the ComPacT range, specifically the ComPacT NSX series."},{"question":"What is C25H34V100's listed depth?","answer":"The depth is 86 mm."},{"question":"What compliance documentation does this brand provide for C25H34V100?","answer":"The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. Standard compliance documentation (declaration of conformity, RoHS, REACH) is available from Schneider Electric's product documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25H34V100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25H34V100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}