{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25H3MA150","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25H3MA150","canonicalUrl":"https://aoctrl.com/schneider/C25H3MA150","factsUrl":"https://aoctrl.com/api/mcp/products/C25H3MA150","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX250H, circuit breaker, 3P, 150 A, MA magnetic trip unit, 100 kA Icu at 240 V AC.","salesMarkdown":"It carries a 100 kA Icu at 240 V AC and 70 kA Icu at 415 V AC per EN/IEC 60947-2, so it safely interrupts high fault currents on motor branch circuits without cascading upstream. The MA trip responds only to short-circuit events — no thermal overload element — meaning the upstream motor starter or soft starter handles the overload protection. The 3D protected poles description indicates all three poles are protected. Breaking capacity varies with system voltage: 100 kA at 240 V, 70 kA at 415 V, 65 kA at 440 V, 50 kA at 500 V, 35 kA at 525 V, and 10 kA at 690 V AC. Under UL 60947-4-1 it is rated 85 kA at 240 V, 65 kA at 480 V, and 15 kA at 600 V AC. This makes the H breaking capacity code suitable for high-fault installations like large motor control centres. IP40 enclosure protection and IK07 impact resistance suit it for panel mounting where occasional tool contact is expected.","metaTitle":"Schneider Electric C25H3MA150 ComPacT NSX 150A MCCB, 100 kA","metaDescription":"Schneider Electric C25H3MA150 ComPacT NSX 250H MCCB, 150 A magnetic-only trip, 100 kA Icu at 240 V. Motor protection, EN/IEC 60947-2. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$415.70","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/083bf7c6094d88e9834271779a81ccc7.pdf","sourceUrl":"https://www.se.com/th/en/product/C25H3MA150/circuit-breaker-compact-nsx250h-70ka-415vac-3-poles-ma-trip-unit-150a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25H3MA150/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25H3MA150","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25H3MA150 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}