{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25N32D100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25N32D100","canonicalUrl":"https://aoctrl.com/schneider/C25N32D100","factsUrl":"https://aoctrl.com/api/mcp/products/C25N32D100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider C25N32D100 Compact Nsx, New Generation — now discontinued. Supplied from remaining channel stock; full specifications, lifecycle and same-series options are below.","salesMarkdown":"## Overview The C25N32D100 is a Schneider ComPacT NSX molded case circuit breaker rated 100 A at 40 °C with a 90 kA breaking capacity at 690 V AC. This 3-pole unit uses a MicroLogic 2.2 electronic trip unit providing L (long-time), So (short-time with fixed delay), and I (instantaneous) protection for distribution applications. It is a fixed-mount design with a toggle control and complies with EN/IEC 60947-2.","metaTitle":"Schneider C25N32D100 ComPacT NSX MCCB, 100 A, 90 kA, 3-pole","metaDescription":"Schneider C25N32D100 ComPacT NSX MCCB, 100 A, 90 kA breaking capacity at 690 V AC, 3-pole, MicroLogic 2.2 electronic trip unit, EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX250N","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"N 50 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"17.6 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$419.12","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9418c2fd8e55cc578d4efea9e22823cc.pdf","sourceUrl":"https://www.se.com/ph/en/product/C25N32D100/circuit-breaker-compact-nsx250n-50ka-at-415vac-micrologic-2-2-trip-unit-100a-3-poles-3d/"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25N32D100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25N32D100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}