{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25N32D250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25N32D250","canonicalUrl":"https://aoctrl.com/schneider/C25N32D250","factsUrl":"https://aoctrl.com/api/mcp/products/C25N32D250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, NSX250N, 3P, 250 A at 40 °C, MicroLogic 2.2 electronic trip unit, 50 kA Icu at 415 V AC.","salesMarkdown":"The Schneider Electric C25N32D250 is a ComPacT NSX250N 3-pole moulded-case circuit breaker rated 250 A at 40 °C, fitted with a MicroLogic 2.2 electronic trip unit. The 2.2 provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection — the So curve is what sets it apart from a basic thermal-magnetic breaker: it coordinates with downstream devices in a selective distribution scheme, letting a fault on a branch trip the branch breaker without dropping the main. The 50 kA Icu at 415 V AC (IEC 60947-2) means it can safely interrupt a fault current up to that level at common industrial voltages; at 690 V the same breaker still holds 10 kA Icu, useful for 690 V distribution in mining or heavy process plants. ## Where it fits and how it mounts Current-production part per the manufacturer's lifecycle status. The C25N32D250 is actively manufactured.","metaTitle":"Schneider Electric C25N32D250 ComPacT NSX250N, 250 A, 50 kA","metaDescription":"Schneider Electric C25N32D250 ComPacT NSX250N 3P circuit breaker, 250 A at 40 °C, MicroLogic 2.2 trip unit, 50 kA Icu at 415 V AC. Active production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$523.26","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/817ce6cd32270bc83aedf553023aa7ef.pdf","sourceUrl":"https://www.se.com/hk/en/product/C25N32D250/circuit-breaker-compact-nsx250n-50ka-415vac-3-poles-micrologic-2-2-trip-unit-250a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25N32D250/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25N32D250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25N32D250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}