{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25N34V100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25N34V100","canonicalUrl":"https://aoctrl.com/schneider/C25N34V100","factsUrl":"https://aoctrl.com/api/mcp/products/C25N34V100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, earth leakage circuit breaker, 3P, 100 A at 40 °C, MicroLogic 4.2 electronic trip unit, 50 kA Icu at 415 V AC.","salesMarkdown":"It carries a MicroLogic 4.2 electronic trip unit that covers overload (L), short-time short-circuit with fixed delay (So), instantaneous short-circuit (I), and integrated earth-leakage (R) protection — all in one device. That means a single breaker handles both overcurrent and ground-fault protection, which simplifies panel wiring and saves a slot compared to a separate GFCI module. Breaking capacity is 50 kA Icu at 380/415 V AC and 440 V AC per IEC 60947-2, with 85 kA Icu at 240 V AC per UL 60947-4-1. For a 100 A frame, 50 kA at 415 V gives you solid headroom on most North American and European distribution panels — you won't be chasing fault-current coordination issues on a typical 400 V line feeding motor control centers or lighting panels. It's meant for a clean indoor electrical room, not a washdown zone. ## The MicroLogic 4.2 trip unit — what the settings mean for your line The earth-leakage function is built in, adjustable via the IΔn rotary switch. That 20-minute thermal memory before and after tripping means the breaker remembers a prior overload — if you're resetting after a stall on a conveyor, the trip curve shifts to protect the cable, not just the motor. Category A utilization (no intentional short-time delay for selectivity with downstream breakers) means this breaker trips fast on a short circuit. If you need zone-selective interlocking, you'd step up to a Category B breaker. For a standalone feeder or branch protection, Category A is fine. Electrical durability is 20,000 cycles at 440 V at half rated current, 10,000 cycles at full rated current. That's typical for a molded-case breaker — good for thousands of manual switching operations on a disconnect, but not rated for continuous motor starting duty. Use a contactor for that.","metaTitle":"Schneider Electric C25N34V100 ComPacT NSX 100A Earth Leakage","metaDescription":"Schneider Electric C25N34V100 ComPacT NSX 100A earth leakage circuit breaker with MicroLogic 4.2 electronic trip unit. 50 kA Icu at 415 V AC. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,210.66 – $2,651.40","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9d43c1fa9a1f1eb629b881b60177d753.pdf","sourceUrl":"https://www.se.com/ae/en/product/C25N34V100/circuit-breaker-compact-nsx250n-50ka-at-415vac-micrologic-4-2-vigi-trip-unit-100a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25N34V100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25N34V100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25N34V100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}