{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25V32D160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25V32D160","canonicalUrl":"https://aoctrl.com/schneider/C25V32D160","factsUrl":"https://aoctrl.com/api/mcp/products/C25V32D160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, C25V32D160, 3P circuit breaker, 160 A rated current, 85 kA Icu at 500 V AC, MicroLogic 2.2 electronic trip unit.","salesMarkdown":"The C25V32D160 is a Schneider Electric ComPacT NSX circuit breaker, part of the ComPacT range, rated 160 A at 40 °C with a MicroLogic 2.2 electronic trip unit. The 3-pole (3P) configuration suits three-phase distribution panels, and the electronic trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection curves, giving selectivity coordination flexibility. Mounts on a backplate (not DIN rail) — horizontal or vertical orientation, flat on the back. The 105 mm width and 161 mm height fit standard ComPacT NSX cutouts; depth is 86 mm. Front connections both upside and downside simplify busbar or cable routing. The toggle control type provides local manual operation. Five accessory slots allow for auxiliary contacts, shunt trips, or communication modules without removing the breaker from the panel. ## Environmental and durability IP40 enclosure keeps out tools and wires larger than 1 mm; IK07 impact resistance covers accidental hammer strikes. Electrical durability: 20,000 cycles at 440 V In/2, 10,000 at 440 V In, 5,000 at 690 V In.","metaTitle":"Schneider Electric C25V32D160 ComPacT NSX 160A, 85kA","metaDescription":"Schneider Electric C25V32D160 ComPacT NSX circuit breaker, 160A rated current, 85 kA Icu at 500 V AC, MicroLogic 2.2 trip unit, 3P, EN/IEC 60947-2. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C25V32D160","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker ComPacT NSX250HB1. 75kA at 690VAC. MicroLogic 2.2 trip unit 160A. 3 poles 3d","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"160 A at 40 °C","Breaking capacity":"85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX250HB1","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"160 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"HB1 75 kA 690 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"17.6 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"63...160 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"2400 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$8.85","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/801e9fa145e5de442d7f3f1fcd730475.pdf","sourceUrl":"https://www.se.com/za/en/product/C25V32D160/circuit-breaker-compact-nsx250hb1-75ka-at-690vac-micrologic-2-2-trip-unit-160a-3-poles-3d/"},"ai":{"faq":[{"question":"Where can I buy C25V32D160 and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm landed-cost figure."},{"question":"What is C25V32D160's breaking capacity at 690 V?","answer":"75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2. This is the HB1 breaking capacity code."},{"question":"What compliance documentation does this brand provide for C25V32D160?","answer":"The breaker carries EN/IEC 60947-2 certification, IP40 protection, and suitability for isolation per the same standard. Schneider Electric provides standard RoHS, REACH, and UL declarations for the ComPacT NSX range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25V32D160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25V32D160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}