{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25V36E100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25V36E100","canonicalUrl":"https://aoctrl.com/schneider/C25V36E100","factsUrl":"https://aoctrl.com/api/mcp/products/C25V36E100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, 100 A, MicroLogic 6.2 E electronic trip unit, 85 kA Icu at 500 V AC, 3-pole, toggle control, LCD display, backplate mount.","salesMarkdown":"The Schneider Electric C25V36E100 is a ComPacT NSX moulded-case circuit breaker rated 100 A at 40 °C with a MicroLogic 6.2 E electronic trip unit. The 6.2 E provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection — the G channel is the key differentiator from the 2.2 or 5.2 trip units, making this breaker suited for applications where ground-fault coordination is required, such as distribution panels feeding sensitive loads or sub-distribution in commercial buildings. ## Breaking capacity and selectivity headroom The HB1 breaking capacity code delivers 85 kA Icu at 500 V AC, 80 kA at 525 V, and 75 kA at 690 V, all per IEC 60947-2. The 75 kA at 690 V is useful for 690 V distribution systems common in mining, marine, and heavy industrial installations. Mounts on a backplate in horizontal or vertical orientation. IP40 enclosure protection and IK07 impact rating suit panel installation where occasional front-panel access is needed. The 35 mm connection pitch matches standard busbar and cable-lug spacing. Front-connect terminals on both line and load sides simplify busbar run and cable dressing within the enclosure. ## Trip unit and metering capability The MicroLogic 6.2 E includes an energy meter function and communicates instantaneous and demand values, demand current and power, maximeters/minimeters, power quality data, protection and alarm settings, energy metering, time-stamped histories, event tables, and maintenance indicators. The LCD display provides local readout of these values without needing a separate power meter. ## Environmental and durability Electrical durability is 20,000 cycles at 440 V at half-rated current, 10,000 cycles at full rated current, and 5,000 cycles at 690 V full current. Relative humidity range 0–95%.","metaTitle":"C25V36E100 ComPacT NSX 100A, MicroLogic 6.2 E, 85 kA","metaDescription":"C25V36E100 ComPacT NSX 100A MCCB with MicroLogic 6.2 E trip unit, 85 kA Icu at 500 V AC. EN/IEC 60947-2. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","Control type":"Toggle","Display type":"LCD display","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 6.2 E","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX250HB1","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Type of measurement":"Energy meter","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Communication of data":"Instantaneous and demand values Demand current and power Maximeters/minimeters Power quality Protection and alarm settings Energy metering Time-stamped histories and event tables Maintenance indicators","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"HB1 75 kA 690 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"17.6 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"With","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"15...400 s at 1.5 x Ir 0.5...16 s at 6 x Ir 0.35...11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","[Tsd] Short-Time Delay Adjustment Range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","[Ig] ground-fault pick-up adjustment range":"0.4...1 x In for In = 40 A 0.2...1 x In for In > 40 A Ig enable on/off","Long-time protection delay adjustment type tr":"Adjustable","[tg] Ground-fault time delay adjustment range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Short-time protection delay adjustment type tsd":"Adjustable 5 settings","Short-time protection pick-up adjustment type Isd":"Adjustable","Ground-fault protection pick-up adjustment type Ig":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","Ground-fault protection time delay adjustment type tg":"Adjustable 5 settings","[Ii] instantaneous protection pick-up adjustment range":"1.5...15 x In","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,233.84","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cc423e8b06dc2a6ef60d19437aed940e.pdf","sourceUrl":"https://www.se.com/au/en/product/C25V36E100/circuit-breaker-compact-nsx250hb1-75ka-690vac-3-poles-micrologic-6-2e-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25V36E100/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for C25V36E100?","answer":"Submit an RFQ through the storefront. The part is sourced to order through independent distribution; current pricing and availability are confirmed at quote time."},{"question":"What is the breaking capacity of C25V36E100?","answer":"85 kA Icu at 500 V AC, 80 kA at 525 V, and 75 kA at 690 V, all per IEC 60947-2. The HB1 code indicates a high-interrupting rating for this 100 A frame."},{"question":"What protection functions does the MicroLogic 6.2 E trip unit provide?","answer":"It provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection. The G channel enables ground-fault coordination, which the 2.2 and 5.2 trip units lack."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25V36E100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25V36E100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}