{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25V36E100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25V36E100","canonicalUrl":"https://aoctrl.com/schneider/C25V36E100","factsUrl":"https://aoctrl.com/api/mcp/products/C25V36E100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, 100 A, MicroLogic 6.2 E electronic trip unit, 85 kA Icu at 500 V AC, 3-pole, toggle control, LCD display, backplate mount.","salesMarkdown":"The Schneider Electric C25V36E100 is a ComPacT NSX moulded-case circuit breaker rated 100 A at 40 °C with a MicroLogic 6.2 E electronic trip unit. The 6.2 E provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection — the G channel is the key differentiator from the 2.2 or 5.2 trip units, making this breaker suited for applications where ground-fault coordination is required, such as distribution panels feeding sensitive loads or sub-distribution in commercial buildings. ## Breaking capacity and selectivity headroom The HB1 breaking capacity code delivers 85 kA Icu at 500 V AC, 80 kA at 525 V, and 75 kA at 690 V, all per IEC 60947-2. The 75 kA at 690 V is useful for 690 V distribution systems common in mining, marine, and heavy industrial installations. Mounts on a backplate in horizontal or vertical orientation. IP40 enclosure protection and IK07 impact rating suit panel installation where occasional front-panel access is needed. The 35 mm connection pitch matches standard busbar and cable-lug spacing. Front-connect terminals on both line and load sides simplify busbar run and cable dressing within the enclosure. ## Trip unit and metering capability The MicroLogic 6.2 E includes an energy meter function and communicates instantaneous and demand values, demand current and power, maximeters/minimeters, power quality data, protection and alarm settings, energy metering, time-stamped histories, event tables, and maintenance indicators. The LCD display provides local readout of these values without needing a separate power meter. ## Environmental and durability Electrical durability is 20,000 cycles at 440 V at half-rated current, 10,000 cycles at full rated current, and 5,000 cycles at 690 V full current. Relative humidity range 0–95%.","metaTitle":"C25V36E100 ComPacT NSX 100A, MicroLogic 6.2 E, 85 kA","metaDescription":"C25V36E100 ComPacT NSX 100A MCCB with MicroLogic 6.2 E trip unit, 85 kA Icu at 500 V AC. EN/IEC 60947-2. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,233.84","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cc423e8b06dc2a6ef60d19437aed940e.pdf","sourceUrl":"https://www.se.com/au/en/product/C25V36E100/circuit-breaker-compact-nsx250hb1-75ka-690vac-3-poles-micrologic-6-2e-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25V36E100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25V36E100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25V36E100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}