{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25W3TM125","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25W3TM125","canonicalUrl":"https://aoctrl.com/schneider/C25W3TM125","factsUrl":"https://aoctrl.com/api/mcp/products/C25W3TM125","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, circuit breaker, 125 A at 40 °C, 3P, TM-D thermal-magnetic trip unit, 100 kA Icu at 500 V AC, backplate mount, IP40.","salesMarkdown":"The 3-pole design (3P) and 100 kA Icu at 500 V AC (50/60 Hz) per IEC 60947-2 mean it can safely interrupt fault currents up to 100 kA without upstream cascading — critical for high-fault-capacity distribution panels where selectivity with upstream devices is required. The thermal-magnetic trip provides L (overload) and I (short-circuit) protection in one unit, so you get both time-delayed thermal response and instantaneous magnetic trip without a separate relay. Rated for 125 A continuous at 40 °C. Breaking capacity holds at 100 kA Icu across 500 V, 525 V, and 660/690 V AC. IP40 front face and IK07 impact resistance suit indoor panel environments where accidental tool drops or panel-door impacts are a risk. ## Sourcing and lifecycle — what to expect when you order IP40 and IK07 ratings are factory-tested per IEC 60529 and IEC 62262 respectively. Connection pitch is 35 mm. Mechanical durability is rated at 20,000 cycles; electrical durability varies by load: 20,000 cycles at 440 V at half rated current (In/2), 10,000 cycles at 440 V at full In, and 5,000 cycles at 690 V at full In. The toggle control is manual only — no motor operator or shunt trip is integrated in this base variant.","metaTitle":"Schneider Electric C25W3TM125 ComPacT NSX 125A 3P Thermal-Ma","metaDescription":"Schneider Electric C25W3TM125 ComPacT NSX circuit breaker, 125A rated at 40°C, 3-pole, TM-D thermal-magnetic trip unit, 100 kA Icu at 500V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$6.42","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f42aa74e00a29a18704389a84cc0535a.pdf","sourceUrl":"https://www.se.com/th/en/product/C25W3TM125/circuit-breaker-compact-nsx250hb2-100ka-690vac-3-poles-tmd-trip-unit-125a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25W3TM125/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25W3TM125","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25W3TM125 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}