{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C4047E400","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C4047E400","canonicalUrl":"https://aoctrl.com/schneider/C4047E400","factsUrl":"https://aoctrl.com/api/mcp/products/C4047E400","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, MicroLogic 7.3 E electronic trip unit, 400 A at 40 °C, 4P, LSIR protection with integrated earth-leakage, LCD display, EN/IEC 60947-2.","salesMarkdown":"## Trip unit for a 400 A distribution feeder The Schneider Electric C4047E400 is a MicroLogic 7.3 E electronic trip unit for the ComPacT NSX400...630 molded-case circuit breaker platform. It is rated 400 A at 40 °C (Ir adjustable 160...400 A) and provides LSIR protection: long-time overload (L), short-time short-circuit (S), instantaneous (I), and integrated earth-leakage (R) — all configurable through the onboard LCD display. ## What the LSIR settings mean for coordination The L protection (long-time) pick-up is adjustable 160...400 A with a delay from 15...400 s at 1.5 x Ir — that range lets you set the feeder to ride through motor inrush without nuisance tripping, while still clearing a sustained overload. The S protection (short-time) delay is 0...0.4 s with I²t on or off; turning I²t on gives inverse-time selectivity downstream, off gives fixed-time coordination. The I (instantaneous) pick-up is also adjustable, and the R (earth-leakage) is Class A, adjustable via the rotary switch on the front face. ## Thermal memory and data logging The unit also logs energy metering, time-stamped events, and demand values, accessible through the LCD or via the communication data port. ## Environmental and installation limits Rated for -25...70 °C operating ambient and -40...85 °C storage. IP40 front face. The unit is Class II double-insulated, so no separate protective-earth connection is required on the trip unit itself.","metaTitle":"Schneider C4047E400 MicroLogic 7.3 E Trip Unit, 400 A","metaDescription":"Schneider Electric C4047E400 MicroLogic 7.3 E electronic trip unit for ComPacT NSX400...630. 400 A at 40 °C, LSIR protection, integrated earth-leakage, LCD display. Active producti","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Display Type":"LCD display","Product Status":"Active","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$24.40","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/dfa56be171e4c124ac554f79d154769e.pdf","sourceUrl":"https://www.se.com/za/en/product/C4047E400/trip-unit-micrologic-vigi-7-3e-compact-nsx400-630-4-poles-basic-and-earth-leakage-protections-energy-meter-400a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C4047E400/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C4047E400","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C4047E400 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}