{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C40F32D250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C40F32D250","canonicalUrl":"https://aoctrl.com/schneider/C40F32D250","factsUrl":"https://aoctrl.com/api/mcp/products/C40F32D250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, C40F32D250, 250A, 3P, MicroLogic 2.3 electronic trip unit, 36 kA Icu at 415 V AC, EN/IEC 60947-2.","salesMarkdown":"At 220/240 V AC it's 40 kA Icu; at 440 V AC it's 30 kA Icu; at 500 V AC it's 25 kA Icu; at 525 V AC it's 20 kA Icu; at 660/690 V AC it's 10 kA Icu. For UL 60947-4-1 applications, it's 85 kA Icu at 240 V AC, 35 kA Icu at 480 V AC, and 20 kA Icu at 600 V AC. This is a Category A breaker — it's not intended for deliberate short-time delay coordination downstream, but the MicroLogic 2.3's So (short-time) protection with fixed delay gives you some selectivity window against downstream instantaneous trips. ## Trip unit and protection The MicroLogic 2.3 electronic trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous) protection. The trip unit is rated 250 A at 40 °C; derate for higher ambient or enclosed mounting. Local signalling includes a flashing green LED for ready-to-operate, a red LED at 105% Ir for overload, and an orange LED at 90% Ir for pre-alarm. ## Mounting and environment Mounts on a backplate in horizontal or vertical orientation, flat on the back. IP40 protects against tools and small wires; IK07 resists 2 J impact. Operates at 0 to 2000 m without derating, 2000 to 5000 m with derating. Relative humidity 0 to 95%.","metaTitle":"C40F32D250 ComPacT NSX 250A 3P MCCB, 36kA 415V","metaDescription":"Schneider Electric C40F32D250 ComPacT NSX circuit breaker, 250A, 3P, MicroLogic 2.3 trip unit, 36kA at 415V AC. Current production, sourced to order. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"110 mm","Width":"140 mm","Height":"255 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In","Mechanical Life Cycles":"15000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$735.59","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1dd0a28c1ac945378fc1e924d1a6a841.pdf","sourceUrl":"https://www.se.com/sg/en/product/C40F32D250/circuit-breaker-compact-nsx400f-36ka-415vac-3-poles-micrologic-2-3-trip-unit-250a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C40F32D250/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C40F32D250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C40F32D250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}