{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C40N32M320","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C40N32M320","canonicalUrl":"https://aoctrl.com/schneider/C40N32M320","factsUrl":"https://aoctrl.com/api/mcp/products/C40N32M320","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX400N, circuit breaker, 3P, 320 A at 65 °C, 85 kA Icu at 240 V AC, MicroLogic 2.3 M electronic trip unit, motor protection application.","salesMarkdown":"The C40N32M320: The 85 kA Icu at 240 V AC and 50 kA at 415 V AC mean this breaker can safely interrupt a fault current up to those levels without welding contacts or rupturing the housing. At 690 V AC it still holds 10 kA Icu. For a motor protection circuit on a 480 V supply (common in North American plants), the 50 kA Icu at 480 V AC per UL 60947-4-1 covers most service-entrance and downstream feeder applications — you won't need a current-limiting fuse upstream unless the available fault current exceeds that figure. ## Motor protection trip curve and thermal memory The MicroLogic 2.3 M provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous) protection, with selectable motor tripping classes 5, 10, and 20. The 20-minute thermal memory before and after tripping means the breaker 'remembers' prior heating — critical for motor starts in quick succession where a cold-start trip curve would allow a second start that a hot motor shouldn't get. This prevents nuisance trips on restart while still protecting the motor winding.","metaTitle":"Schneider Electric C40N32M320 ComPacT NSX400N, 320 A, 85 kA","metaDescription":"Schneider Electric C40N32M320 ComPacT NSX400N circuit breaker, 320 A at 65 °C, 85 kA Icu at 240 V AC, MicroLogic 2.3 M trip unit, motor protection, EN/IEC 60947-2, IP40. Available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"110 mm","Width":"140 mm","Height":"255 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In","Mechanical Life Cycles":"15000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$847.57","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/93575d455dc3fe84f726deab4e28baba.pdf","sourceUrl":"https://www.se.com/za/en/product/C40N32M320/circuit-breaker-compact-nsx400n-50ka-at-415vac-micrologic-2-3-m-trip-unit-320a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C40N32M320/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C40N32M320","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C40N32M320 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}