{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60FM","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60FM","canonicalUrl":"https://aoctrl.com/schneider/C60FM","factsUrl":"https://aoctrl.com/api/mcp/products/C60FM","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, ComPacT NS630b–NS3200, MicroLogic 6.0 control unit, 630–3200 A, selective + earth-fault protection, IEC 60947-4-2.","salesMarkdown":"## MicroLogic 6.0 control unit for ComPacT NS630b–NS3200 The C60FM is the MicroLogic 6.0 electronic control unit for Schneider Electric's ComPacT NS630b–NS3200 new-generation air circuit breakers. It provides selective (L, S, I) plus earth-fault (G) protection, with the trip unit rating adjustable from 630 A up to 3200 A at 50 °C. The unit is designed for fixed-mounted breakers on 50/60 Hz AC distribution networks. ## Protection settings and adjustability Long-time pickup (Ir) is adjustable over 0.4–1.0 x In in nine steps, with delay (tr) settable from 0.7–16.6 s at 7.2 x Ir or 12.5–600 s at 1.5 x Ir. Short-time pickup (Isd) covers 1.5–10 x Ir, also nine steps, with delay (tsd) 0–0.4 s (I²t on or off). Instantaneous pickup (Ii) is adjustable from 2–15 x In, or can be switched off entirely. Earth-fault pickup (Ig) ranges from 0.2–1.0 x In (for In ≤ 1250 A), delay (tg) 0–0.4 s (I²t on or off). All adjustments are made via the front-panel dials — no software or programming tool is required. ## Status and fault signalling Three red LEDs indicate the type of electrical fault (overload, short-circuit, earth fault); a separate red LED flags an internal trip-unit error, and a yellow LED signals an overload pre-alarm. The thermal memory (20-minute time constant) retains the thermal state after a trip, preventing immediate reclosure onto a still-hot conductor. Rated per IEC 60947-4-2, the standard for circuit-breaker control units. The unit is designed for distribution applications and supports 3-pole, 4-pole, and 3-pole + half-neutral (3t + N/2) configurations.","metaTitle":"Schneider Electric C60FM MicroLogic 6.0 Control Unit, ComPac","metaDescription":"Schneider Electric C60FM MicroLogic 6.0 control unit for ComPacT NS630b–NS3200. Selective + earth-fault protection, 630–3200 A, IEC 60947-4-2. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Standards":"IEC 60947-4-2","Network type":"AC","Thermal memory":"20 mn","Trip unit name":"MicroLogic 6.0","Number of poles":"3P 4P","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for earth fault","lifecycle_stage":"current","Local signalling":"3 LEDs (red) for electrical fault 1 LED (red) for internal error 1 LED (yellow) for overload","Range of product":"ComPacT NS630b...1600 new generation ComPacT NS1600b...3200 new generation","Trip unit rating":"630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C","Network frequency":"50/60 Hz","Device application":"Distribution","Trip unit technology":"Electronic","Earth-leakage protection":"Without","Product or component type":"Control unit","Protected poles description":"4t 3t 3t + N/2","Circuit breaker mounting mode":"Fixed","Trip unit protection functions":"Selective + earth-fault protection","Zone selective interlocking ZSI":"Without","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","Long-time protection delay adjustment type tr":"Adjustable 9 settings","Short-time protection delay adjustment type tsd":"Adjustable","[Tr] Long-Time Protection Delay Adjustment Range":"0.7...16.6 s at 7.2 x Ir 0.5...24 s at 6 x Ir 12.5...600 s at 1.5 x Ir","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","Ground-fault protection pick-up adjustment type Ig":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"0.4...1 x In","[tsd] Short-time protection delay adjustment range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Instantaneous protection pick-up adjustment type Ii":"Adjustable 9 settings","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","Ground-fault protection time delay adjustment type tg":"Adjustable","[Ig] ground-fault protection pick-up adjustment range":"0.2...1 x In for 400 A < In < 1250 A 0.3...1 x In for In 500...1200 A for In >= 1250 A","[Ii] instantaneous protection pick-up adjustment range":"2...15 x In Off","[Tg] Ground-Fault Protection Time Delay Adjustment Range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$861.37","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f32d36da2db455c8c756559e32f19062.pdf","sourceUrl":"https://www.se.com/ae/en/product/C60FM/control-unit-micrologic-6-0-compact-ns630b-to-ns3200-fixed-manually-operated-selective-and-earthfault-protections/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60FM/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60FM and how do I get a price?","answer":"The C60FM is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing."},{"question":"What is C60FM's listed range (ComPacT) on this component line?","answer":"The C60FM belongs to the ComPacT range, specifically the ComPacT NS630b–NS1600 new generation and ComPacT NS1600b–NS3200 new generation series."},{"question":"What is C60FM's listed standards (IEC 60947-4-2) on this component line?","answer":"The C60FM is certified to IEC 60947-4-2, the standard for control units of circuit-breakers used in distribution networks."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60FM","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60FM when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}