{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H1P16AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H1P16AC","canonicalUrl":"https://aoctrl.com/schneider/C60H1P16AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H1P16AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H series, C60H1P16AC, miniature circuit breaker, 1-pole, 16 A, C-curve, 15 kA breaking capacity at 230 V AC, DIN rail mount.","salesMarkdown":"## What this MCB does in the panel The Schneider Electric C60H1P16AC is a 1-pole miniature circuit breaker from the Multi9 C60H series, rated 16 A at 30 °C with a C-curve magnetic trip (5...10 x In). Breaking capacity is 15 kA Icu at 230...240 V AC (IEC 60947-2), with a corresponding Ics of 15 kA at 440 V AC — meaning it can clear a fault and be reclosed at that level without replacement. Mounts fixed on 35 mm DIN rail. The toggle provides local ON/OFF indication, and a contact position indicator confirms isolation status — the breaker is certified for isolation use per IEC 60947-2. Operating temperature range is -25 to 60 °C, with 95 % relative humidity tolerance at 55 °C (tropicalisation per IEC 60068-1). Suitable for installation at altitudes up to 2000 m.","metaTitle":"Schneider Electric C60H1P16AC MCB, C-Curve 16 A 1P, 15 kA","metaDescription":"Schneider Electric C60H1P16AC miniature circuit breaker, 16 A rated, C-curve, 1-pole, 15 kA breaking capacity at 230 V AC. Multi9 range, DIN rail mount. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"18 mm","Height":"81 mm","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"16 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"5...10 x In","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 2 kA conforming to IEC 60947-2 AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H1P16AC/miniature-circuit-breaker-c60h-1-pole-16-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H1P16AC/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60H1P16AC and what is the lead time?","answer":"The C60H1P16AC is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of C60H1P16AC at 230 V?","answer":"The C60H1P16AC has a breaking capacity of 15 kA Icu at 230...240 V AC (IEC 60947-2). The corresponding service breaking capacity Ics is 15 kA at 440 V AC."},{"question":"What is the closest alternative to C60H1P16AC in the same family?","answer":"Within the Multi9 C60H series, the closest peer is the same 1-pole C-curve breaker at a different current rating. For a 16 A 1-pole C-curve MCB, the C60H1P16AC is the direct order code; no pin-compatible alternative exists because the rating is the defining parameter."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H1P16AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H1P16AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}