{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H1P2AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H1P2AC","canonicalUrl":"https://aoctrl.com/schneider/C60H1P2AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H1P2AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60 series, C60H1P2AC miniature circuit-breaker, 2 A rated current, C-curve, 1-pole, 15 kA breaking capacity at 230-240 V AC.","salesMarkdown":"The Schneider Electric C60H1P2AC is a 2 A, 1-pole miniature circuit breaker from the Multi9 C60 series, with a C-curve trip characteristic (magnetic tripping at 5–10× In). The thermal-magnetic trip unit protects against overload and short-circuit, with a breaking capacity of 15 kA Icu at 230–240 V AC 50/60 Hz per IEC 60947-2 — enough for most commercial and light industrial panelboards. The 2 A rated current (at 30 °C) sets the continuous load limit for the protected circuit — sized for lighting or control circuits drawing under 2 A, not motor or power feeders. The C-curve (5–10× In) means the magnetic trip holds through moderate inrush, so it suits transformer or capacitive loads that see a short current spike on energization. The 1-pole construction protects a single phase or line conductor. The 18 mm width (2 modules) fits standard distribution board cutouts. Wire stripping length is 14 mm. The toggle switch provides local ON/OFF indication and a contact position indicator confirms the state of the contacts.","metaTitle":"Schneider Electric C60H1P2AC C60 MCB, 2 A, Curve C, 1P, 15 k","metaDescription":"Schneider Electric C60H1P2AC miniature circuit breaker, 2 A rated, C-curve, 1-pole, 15 kA breaking capacity at 230-240 V. Multi9 range, DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"18 mm","Height":"81 mm","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"2 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"5...10 x In","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 2 kA conforming to IEC 60947-2 AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H1P2AC/miniature-circuit-breaker-c60h-1-pole-2-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H1P2AC/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60H1P2AC and get a price?","answer":"The C60H1P2AC is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is the breaking capacity of C60H1P2AC?","answer":"The C60H1P2AC has a breaking capacity of 15 kA Icu at 230–240 V AC 50/60 Hz per IEC 60947-2, with higher ratings at lower voltages (20 kA at 60 V DC, 30 kA at 130 V AC) and a lower rating of 4 kA at 400–415 V AC."},{"question":"What compliance documentation does Schneider provide for C60H1P2AC?","answer":"The C60H1P2AC carries IEC 60947-2 certification for breaking capacity and service breaking capacity, with suitability for isolation per that standard. It also conforms to IEC 60068-1 for tropicalisation (class 2). The product is part of the Multi9 range and is designed for distribution applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H1P2AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H1P2AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}