{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H1P2AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H1P2AD","canonicalUrl":"https://aoctrl.com/schneider/C60H1P2AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H1P2AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, Multi9 range, C60H1P2AD, miniature circuit breaker, D curve, 2 A, 1P, 15 kA at 230 V AC.","salesMarkdown":"The Schneider Electric C60H1P2AD is a 1-pole miniature circuit breaker from the Multi9 C60 range, rated 2 A with a D tripping curve. The thermal-magnetic trip unit handles the overload side; the magnetic element handles short-circuit. ## Breaking capacity and service continuity Rated Icu of 15 kA at 230...240 V AC and 4 kA at 400...415 V AC, both per IEC 60947-2. At 60 V DC the Icu is 20 kA (1P), and at 130 V AC it reaches 30 kA. The limitation class is 3, so it lets through less fault energy than a standard Class 2 breaker, reducing stress on downstream components. Snaps onto 35 mm symmetrical DIN rail, occupies 2 modules (18 mm per pitch). Depth is 73 mm, height 81 mm. Rated for operation from -25 °C to 60 °C, storage from -40 °C to 70 °C, with 95 % relative humidity at 55 °C. Tropicalisation per IEC 60068-1 is included — the breaker is treated for warm, humid environments without condensation inside the enclosure. Operating altitude is rated to 2000 m.","metaTitle":"Schneider C60H1P2AD MCB, D Curve 2 A, 1P, 15 kA","metaDescription":"Schneider Electric C60H1P2AD miniature circuit breaker, Multi9 range, D curve, 2 A rated, 1 pole, 15 kA breaking capacity at 230 V AC. DIN rail mount. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"18 mm","Height":"81 mm","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"2 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"10...14 x In","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 2 kA conforming to IEC 60947-2 AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H1P2AD/miniature-circuit-breaker-c60h-1-pole-2-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H1P2AD/alternatives.json"},"ai":{"faq":[{"question":"What is C60H1P2AD's breaking capacity at 230 V?","answer":"The C60H1P2AD has a rated Icu of 15 kA at 230...240 V AC, 50/60 Hz, conforming to IEC 60947-2."},{"question":"What does the D curve mean on this breaker?","answer":"The D curve means the magnetic trip threshold is 10 to 14 times the rated current (2 A), so it tolerates the high inrush of motor or transformer loads without nuisance tripping."},{"question":"Where can I buy C60H1P2AD?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H1P2AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H1P2AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}