{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H1P40AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H1P40AD","canonicalUrl":"https://aoctrl.com/schneider/C60H1P40AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H1P40AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H series, C60H1P40AD miniature circuit breaker, D-curve, 40 A, 1-pole, 15 kA breaking capacity at 230-240 V AC.","salesMarkdown":"The C60H1P40AD is a 1-pole miniature circuit breaker from Schneider Electric's Multi9 C60 range, rated 40 A at 40 °C with a D tripping curve. Mounts fixed on 35 mm DIN rail — no adapter plate needed. Tunnel-type terminals accept up to 25 mm² flexible or 35 mm² rigid copper; strip length is 14 mm, tighten to 3.5 N·m. The toggle gives local ON/OFF indication with a contact position indicator, so a panel walk-down confirms isolation state without a meter.","metaTitle":"C60H1P40AD Miniature Circuit Breaker, D Curve, 40 A, 1 Pole","metaDescription":"C60H1P40AD from Schneider Electric's Multi9 range. D-curve thermal-magnetic MCB, 40 A, 1-pole, 15 kA breaking capacity at 230-240 V. Current lifecycle stage, sourced to order. Requ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"18 mm","Height":"81 mm","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"40 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"10...14 x In","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 2 kA conforming to IEC 60947-2 AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H1P40AD/miniature-circuit-breaker-c60h-1-pole-40-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H1P40AD/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for C60H1P40AD?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels. No stock count or price is published here, but a quote typically returns within the same business day."},{"question":"What is C60H1P40AD's listed depth?","answer":"The depth is 73 mm. Combined with the 18 mm width (2 x 9 mm pitches) and 81 mm height, it occupies a standard single-module footprint on 35 mm DIN rail."},{"question":"What compliance documentation does this brand provide for C60H1P40AD?","answer":"The part is designed to IEC 60947-2 for breaking capacity, insulation, and isolation suitability. It carries tropicalisation per IEC 60068-1. RoHS and REACH declarations, plus UL/CSA certifications where applicable, are available on request with your order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H1P40AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H1P40AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}