{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H1P50AB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H1P50AB","canonicalUrl":"https://aoctrl.com/schneider/C60H1P50AB","factsUrl":"https://aoctrl.com/api/mcp/products/C60H1P50AB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60, C60H1P50AB, miniature circuit breaker, 1P, 50 A, B curve, 15 kA breaking capacity at 230 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The Schneider Electric C60H1P50AB is a 1-pole miniature circuit breaker from the Multi9 C60 series, rated 50 A at 30 °C with a B-curve trip characteristic (3 to 5 × In magnetic tripping limit). ## Breaking capacity and what it means for your panel The C60H1P50AB carries a 15 kA Icu at 230…240 V AC (IEC 60947-2) and a 10 kA Icn at 230/400 V AC (EN 60898). At 60 V DC it holds 20 kA Icu. The C60H1P50AB is certified to IEC 60947-2 and EN 60898. It is suitable for isolation per IEC 60947-2, with a rated impulse withstand voltage of 6 kV.","metaTitle":"Schneider Electric C60H1P50AB C60 MCB, 1P, 50 A, B Curve, 15","metaDescription":"Schneider Electric C60H1P50AB miniature circuit breaker, 1P, 50 A, B curve, 15 kA breaking capacity at 230 V AC. IEC 60947-2 and EN 60898. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"18 mm","Height":"81 mm","Standards":"IEC 60947-2 EN 60898","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"DC AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m upside 3.5 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"50 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"3...5 x In","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"12...440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"2 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz 25 kA conforming to IEC 60947-2 - 130 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H1P50AB/miniature-circuit-breaker-c60h-1-pole-50-a-b-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H1P50AB/alternatives.json"},"ai":{"faq":[{"question":"What is C60H1P50AB's listed depth?","answer":"The depth is 73 mm."},{"question":"What is C60H1P50AB's range?","answer":"It belongs to the Multi9 range, product name C60."},{"question":"What compliance documentation does this brand provide for C60H1P50AB?","answer":"The breaker is certified to IEC 60947-2 and EN 60898. It carries a rated impulse withstand voltage of 6 kV and is suitable for isolation per IEC 60947-2. Tropicalisation class 2 per IEC 60068-1 and limitation class 3 per IEC 60947-2 are also documented."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H1P50AB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H1P50AB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}