{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H1P50AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H1P50AD","canonicalUrl":"https://aoctrl.com/schneider/C60H1P50AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H1P50AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H1P50AD, Multi9 C60H series, 1-pole miniature circuit breaker, D curve, 50 A rated current, 10 kA Icn at 230/400 V AC, thermal-magnetic trip, 35 mm DIN rail mount.","salesMarkdown":"The Schneider Electric C60H1P50AD is a 1-pole miniature circuit breaker from the Multi9 C60H series, rated 50 A at 40 °C with a D tripping curve. Breaking capacity is 10 kA Icn at 230/400 V AC per EN 60898, and 15 kA Icu at 230–240 V AC per IEC 60947-2. For DC circuits, it handles 20 kA at 60 V DC (1P). These ratings let the C60H1P50AD serve as a main or branch breaker in a residential or light commercial panel, provided the prospective fault current stays within its envelope. ## Installation and compliance The breaker is certified to EN 60898 and IEC 60947-2, with tropicalisation per IEC 60068-1 (2 levels) and limitation class 3 per IEC 60947-2. The toggle provides local ON/OFF indication and a contact position indicator confirms the state of the main contacts.","metaTitle":"C60H1P50AD Miniature Circuit Breaker, D Curve, 50 A, 1P","metaDescription":"Schneider Electric C60H1P50AD C60H MCB, 50 A, D curve, 1-pole, 10 kA Icn, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"18 mm","Height":"81 mm","Standards":"EN 60898 IEC 60947-2","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC DC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m upside 3.5 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"50 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"10...14 x In","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"12...440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"2 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz 25 kA conforming to IEC 60947-2 - 130 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H1P50AD/miniature-circuit-breaker-c60h-1-pole-50-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H1P50AD/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60H1P50AD and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing — no stock or price figures are published here."},{"question":"What does the D curve mean on this breaker?","answer":"The D curve trips magnetically at 10–14 times the rated current (In). For the C60H1P50AD at 50 A, that means instantaneous trip between 500 A and 700 A. This suits loads with high inrush like motors, transformers, and welding equipment."},{"question":"What is the breaking capacity at 400 V?","answer":"At 400–415 V AC, the Icu per IEC 60947-2 is 4 kA, and the Ics (service breaking capacity) is 2 kA. At 230/400 V AC per EN 60898, the Icn is 10 kA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H1P50AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H1P50AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}