{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H1P63AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H1P63AC","canonicalUrl":"https://aoctrl.com/schneider/C60H1P63AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H1P63AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H, miniature circuit breaker, C60H1P63AC, 63 A, C curve, 1 pole, 15 kA at 230 V AC, 35 mm DIN rail.","salesMarkdown":"The C60H1P63AC is a 1-pole miniature circuit breaker from the Multi9 C60H series, rated 63 A at 30 °C with a C-curve trip characteristic (magnetic tripping between 5 and 10 times In). That C curve means it handles moderate inrush — typical for motor starters, lighting banks, and transformer primaries — without nuisance trips, while still clearing short circuits fast enough for most distribution panels. The 15 kA Icu at 230…240 V AC (IEC 60947-2) is the maximum fault current it can safely interrupt; the Ics rating of 7.5 kA at the same voltage tells you it can reclose after a fault at that level without immediate replacement. For 400…415 V AC networks, the Icu drops to 4 kA and the Ics to 2 kA — so on a 400 V three-phase panel, this breaker needs upstream coordination to stay within those limits. That terminal capacity is generous for a 63 A breaker — it lets you land the full-rated conductor without pigtailing or splicing. ## Deployment context It is certified to both IEC 60947-2 (industrial) and EN 60898 (residential/commercial) — so it qualifies for either duty, but the lower Ics at 400 V means it is best applied as a downstream branch breaker, not a main. Rated operational voltage spans 12…440 V AC 50/60 Hz, with a 500 V insulation voltage and 6 kV impulse withstand.","metaTitle":"Schneider Electric C60H1P63AC MCB, C Curve, 63 A, 1P","metaDescription":"Schneider Electric C60H1P63AC miniature circuit breaker, 63 A, C curve, 1 pole, 15 kA breaking capacity at 230 V AC, DIN rail mount, Multi9 range. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"18 mm","Height":"81 mm","Standards":"IEC 60947-2 EN 60898","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC DC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m upside 3.5 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"63 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"5...10 x In","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"12...440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"2 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz 25 kA conforming to IEC 60947-2 - 130 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H1P63AC/miniature-circuit-breaker-c60h-1-pole-63-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H1P63AC/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C60H1P63AC at 230 V?","answer":"15 kA Icu at 230…240 V AC 50/60 Hz per IEC 60947-2, with an Ics (service breaking capacity) of 7.5 kA at the same voltage."},{"question":"What terminals does C60H1P63AC accept?","answer":"Tunnel-type terminals accepting up to 25 mm² flexible or 35 mm² rigid cable, with a tightening torque of 3.5 N.m."},{"question":"Where can I buy C60H1P63AC and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H1P63AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H1P63AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}