{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H1P63AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H1P63AD","canonicalUrl":"https://aoctrl.com/schneider/C60H1P63AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H1P63AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H, C60H1P63AD, miniature circuit breaker, 63 A, D curve, 1 pole, 15 kA Icu at 230-240 V AC, 73 mm depth.","salesMarkdown":"The Schneider Electric C60H1P63AD is a C60H-series miniature circuit breaker from the Multi9 range, rated 63 A at 40 °C with a D tripping curve (10...14 x In magnetic limit). It protects a single pole and is built for distribution panels on 35 mm symmetrical DIN rail, occupying 2 x 9 mm pitches (18 mm wide). The thermal-magnetic trip unit handles both overload and short-circuit faults, with a breaking capacity of 15 kA Icu at 230...240 V AC per IEC 60947-2 and 10 kA Icn at 230/400 V AC per EN 60898. The 15 kA Icu at 230...240 V AC means this breaker can safely interrupt fault currents up to that level without welding or exploding — critical for coordinating with upstream devices in a distribution board. At 400...415 V AC the Icu drops to 4 kA, so verify the prospective short-circuit current at the installation point if feeding a 400 V line. The Ics (service breaking capacity) is 7.5 kA at 230...240 V AC, meaning after clearing a fault at that level the breaker remains functional enough to be reclosed. ## D-curve application At 63 A, the magnetic trip fires between 630 A and 882 A, so it will not nuisance-trip on a motor starting surge that lasts a few cycles. For resistive or general-purpose distribution loads, a C-curve breaker would trip faster on moderate overloads; the D curve trades some sensitivity for inrush immunity. ## Panel integration Snaps onto 35 mm symmetrical DIN rail. The tunnel terminals accept up to 25 mm² flexible or 35 mm² rigid cable, with a tightening torque of 3.5 N.m on both line and load sides. The toggle provides local ON/OFF indication and a contact position indicator confirms the state of the main contacts. Rated for operation from -25 °C to 60 °C and storage from -40 °C to 70 °C. Tropicalisation per IEC 60068-1 (2 levels) means it withstands 95 % relative humidity at 55 °C without condensation damage — suitable for outdoor cabinets in humid climates. The 6 kV rated impulse withstand voltage (Uimp) per IEC 60947-2 ensures the breaker survives transient surges common in industrial networks.","metaTitle":"Schneider C60H1P63AD MCB, 63A D Curve, 1P, Multi9","metaDescription":"Schneider Electric C60H1P63AD miniature circuit breaker, 63 A rated current, D curve, 1 pole, 15 kA breaking capacity at 230-240 V AC. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"18 mm","Height":"81 mm","Standards":"EN 60898 IEC 60947-2","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"DC AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m upside 3.5 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"63 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"10...14 x In","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"12...440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"2 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz 25 kA conforming to IEC 60947-2 - 130 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H1P63AD/miniature-circuit-breaker-c60h-1-pole-63-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H1P63AD/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60H1P63AD and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing at the time of your order."},{"question":"What is C60H1P63AD's listed depth?","answer":"The depth is 73 mm, which fits standard 100 mm deep enclosures with clearance for wiring behind the DIN rail."},{"question":"What is the Multi9 range?","answer":"Multi9 is Schneider Electric's family of DIN-rail miniature circuit breakers and related distribution products. The C60H1P63AD belongs to this range, which includes C60, C60H, and C60N variants differentiated by breaking capacity."},{"question":"What compliance documentation is available for C60H1P63AD?","answer":"The breaker is certified to EN 60898 and IEC 60947-2. It carries a 6 kV rated impulse withstand voltage (Uimp) per IEC 60947-2 and is suitability for isolation per the same standard. The manufacturer typically provides CE declaration, RoHS, and REACH documentation upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H1P63AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H1P63AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}