{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H1P6AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H1P6AD","canonicalUrl":"https://aoctrl.com/schneider/C60H1P6AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H1P6AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H1P6AD, Multi9 C60H series, miniature circuit breaker, 1-pole, 6 A rated current, D curve, 15 kA breaking capacity at 230 V AC, thermal-magnetic trip unit.","salesMarkdown":"The C60H1P6AD is a 1-pole thermal-magnetic miniature circuit breaker from the Multi9 C60 range, rated 6 A at 40 °C with a D tripping curve (10–14 × In magnetic trip limit). Breaking capacity is 15 kA Icu at 230–240 V AC (IEC 60947-2), with a service breaking capacity Ics of 15 kA at 12–440 V AC — meaning it can safely interrupt a fault up to 15 kA and still be usable afterward. At 400 V AC the Icu drops to 4 kA, so if your panel feeds a 400 V bus with a high prospective fault current, this breaker needs upstream current limitation or a higher-rated device. The 6 kV impulse withstand voltage (Uimp) covers typical transient overvoltages in distribution panels. ## DIN rail integration and panel fit Depth is 73 mm, height 81 mm — standard for the C60 family, so it drops into any Multi9 distribution board without a footprint conflict. The toggle switch provides local ON/OFF indication and a contact position indicator confirms isolation status — useful for lockout/tagout verification when the breaker is used as a disconnector (suitability for isolation per IEC 60947-2).","metaTitle":"Schneider C60H1P6AD C60 MCB, 6 A, D Curve, 1 Pole, 15 kA","metaDescription":"Schneider Electric C60H1P6AD miniature circuit breaker, 6 A rated current, D curve, 1 pole, 15 kA breaking capacity at 230 V AC. Multi9 range, DIN rail mount. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"18 mm","Height":"81 mm","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"6 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"10...14 x In","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 2 kA conforming to IEC 60947-2 AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H1P6AD/miniature-circuit-breaker-c60h-1-pole-6-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H1P6AD/alternatives.json"},"ai":{"faq":[{"question":"What is the C60H1P6AD used for?","answer":"It is a miniature circuit breaker for distribution applications, rated 6 A with a D curve, suited for protecting circuits with motor or transformer loads where high inrush current is expected. It mounts on a 35 mm DIN rail and occupies 2 module pitches."},{"question":"What breaking capacity does the C60H1P6AD have?","answer":"The Icu is 15 kA at 230–240 V AC and 4 kA at 400–415 V AC, per IEC 60947-2. The Ics at 12–440 V AC is also 15 kA, meaning the breaker remains usable after clearing a fault at that level."},{"question":"Where can I buy the C60H1P6AD?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H1P6AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H1P6AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}