{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P10AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P10AD","canonicalUrl":"https://aoctrl.com/schneider/C60H2P10AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P10AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H2P10AD, Multi9 C60 series miniature circuit breaker, 1P+N, 10 A rated, D curve, 10 kA breaking capacity at 440 V AC, DIN rail mount.","salesMarkdown":"The Schneider C60H2P10AD is a Multi9 C60 miniature circuit breaker — 1P+N, 10 A rated current at 40 °C, D trip curve. The 36 mm width (4 × 9 mm pitches) fits a 1P+N slot. Neutral is on the left, fixed position. Toggle handle with ON/OFF indication; the contact position indicator confirms isolation visually. ## Trip technology and environment Thermal-magnetic trip unit — the thermal bimetal handles overloads (slow, heat-dependent), the solenoid handles short-circuits (instantaneous above the magnetic threshold). That's enough lug for a 10 A feed plus downstream tap-offs in a distribution board. Rated for -25 to 60 °C operating ambient, 95 % RH at 55 °C. Tropicalisation level 2 per IEC 60068-1 — the part is treated for warm, humid environments (no condensation issues in a non-climate-controlled panel). Altitude limit 2000 m; above that the air density drops and the arc-quenching performance derates, so it's a standard lowland breaker.","metaTitle":"Schneider C60H2P10AD C60 MCB, 10A D Curve, 1P+N, 10kA","metaDescription":"Schneider C60H2P10AD Multi9 C60 MCB, 10A rated, D curve, 1P+N, 10kA breaking capacity at 440V AC. DIN rail mount, thermal-magnetic trip. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Curve code":"D","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"10 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P10AD/miniature-circuit-breaker-c60h-2-poles-10-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P10AD/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C60H2P10AD?","answer":"10 kA Icu at 440 V AC, 15 kA at 400–415 V AC, and 30 kA at 230–240 V AC, all per IEC 60947-2. For DC applications, 25 kA at 125 V DC for 2-pole series connection."},{"question":"What does the D curve mean on this breaker?","answer":"Magnetic trip threshold is 10–14 × In. For the 10 A rating, that means instantaneous trip between 100 A and 140 A — designed for high-inrush loads like motors, transformers, or welding equipment where a B or C curve would trip on startup."},{"question":"Where can I buy C60H2P10AD?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P10AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P10AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}