{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P16AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P16AC","canonicalUrl":"https://aoctrl.com/schneider/C60H2P16AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P16AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H, miniature circuit-breaker, 1P + N, 16 A, C curve, 10 kA breaking capacity at 440 V AC, 35 mm DIN rail mount.","salesMarkdown":"The C60H2P16AC is a 1P + N miniature circuit-breaker from Schneider Electric's Multi9 C60 range, rated 16 A at 30 °C with a C trip curve (5–10 × In magnetic tripping limit). Breaking capacity is 30 kA Icu at 230–240 V AC, 15 kA at 400–415 V AC, and 10 kA at 440 V AC, all conforming to IEC 60947-2. At 125 V DC (2 poles) it delivers 25 kA Icu. That range of SCCR values lets you coordinate selectivity across different fault levels in the distribution panel without oversizing the branch breaker. The separate earth-leakage block (Vigi add-on) is ordered independently when ground-fault protection is required.","metaTitle":"C60H2P16AC Miniature Circuit-Breaker, C Curve, 16 A, Multi9","metaDescription":"C60H2P16AC MCB from Schneider Electric's Multi9 range. 16 A rated current, C curve, 10 kA breaking capacity at 440 V AC. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"16 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"5 kA conforming to IEC 60947-2 AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P16AC/miniature-circuit-breaker-c60h-2-poles-16-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P16AC/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C60H2P16AC at 400 V?","answer":"At 400–415 V AC, the breaking capacity is 15 kA Icu conforming to IEC 60947-2."},{"question":"What is the closest alternative to C60H2P16AC in the same family?","answer":"Within the C60 range, the closest alternative is a different current rating or pole configuration — the C60H2P16AC is a 1P + N, 16 A, C-curve variant. For a 2-pole version at the same current, look at the C60H-DIN series; for a different trip curve (B or D), the C60H prefix remains the same but the curve code changes."},{"question":"What compliance documentation does Schneider provide for C60H2P16AC?","answer":"The MCB carries IEC 60947-2 certification for breaking capacity and isolation suitability. Tropicalisation conforms to IEC 60068-1 class 2. Standard declarations (CE, UKCA, RoHS) are available through Schneider's documentation portal for the Multi9 range."},{"question":"Where can I buy C60H2P16AC and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the latest commercial terms."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P16AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P16AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}