{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P1AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P1AC","canonicalUrl":"https://aoctrl.com/schneider/C60H2P1AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P1AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H, C60H2P1AC, miniature circuit breaker, 1P+N, C curve, 1 A, 10 kA Icu at 440 V AC.","salesMarkdown":"The Schneider Electric C60H2P1AC is a 1P+N miniature circuit breaker from the Multi9 C60 range, rated 1 A with a C curve (magnetic trip at 5–10 x In). The 1 A rating protects a low-current branch; at 30 °C ambient it carries 1 A continuously, and the thermal-magnetic trip handles both overload and short-circuit conditions. Breaking capacity is 10 kA Icu at 440 V AC per IEC 60947-2, with higher ratings at lower voltages: 15 kA at 400–415 V AC, 30 kA at 230–240 V AC. For a 1 A MCB on a typical 230/400 V distribution board, the 10 kA at 440 V is the limiting figure — it confirms the breaker can safely interrupt a fault up to that level without welding contacts or cascading upstream. The 25 kA DC rating at 125 V DC (2P series-connected) is available if the same frame is used in a DC sub-panel. The 1P+N configuration protects the phase only; the neutral pole is switched but not protected. That's standard for single-phase final circuits where the neutral is solidly bonded at the distribution board. The neutral position is left, matching the typical busbar arrangement in Schneider distribution boards. At 4 module pitches (36 mm wide per module, so 144 mm total), it occupies four 18 mm slots in a standard distribution board. Depth is 73 mm, height 81 mm — check enclosure fill factor if the board is tight, but the footprint is standard for a 1P+N MCB in the Multi9 family. The contact position indicator and ON/OFF local signalling give a quick visual check during commissioning or troubleshooting.","metaTitle":"Schneider Electric C60H2P1AC MCB, C Curve, 1P+N, 1 A, 10 kA","metaDescription":"Schneider Electric C60H2P1AC miniature circuit breaker, Multi9 range, C curve, 1P+N, 1 A rated current, 10 kA breaking capacity at 440 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"1 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P1AC/miniature-circuit-breaker-c60h-2-poles-1-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P1AC/alternatives.json"},"ai":{"faq":[{"question":"What is C60H2P1AC's breaking capacity at 440 V AC?","answer":"The C60H2P1AC has a breaking capacity of 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2. At 230–240 V AC the rating rises to 30 kA Icu."},{"question":"What does the C curve mean on this MCB?","answer":"The C curve means the magnetic trip operates at 5–10 times the rated current (In). For a 1 A breaker, that's 5–10 A instantaneous trip — suitable for general-purpose distribution circuits with moderate inrush, like lighting and small transformers."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P1AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P1AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}