{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P1AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P1AD","canonicalUrl":"https://aoctrl.com/schneider/C60H2P1AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P1AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H miniature circuit breaker, 1P+N, 1 A rated current, D curve, 10 kA breaking capacity at 440 V AC, thermal-magnetic trip, 35 mm DIN rail mount.","salesMarkdown":"The Schneider Electric C60H2P1AD is a 1P+N miniature circuit breaker from the Multi9 C60 range, rated 1 A at 40 °C with a D tripping curve (magnetic trip 10–14 x In). It breaks up to 10 kA at 440 V AC (Icu per IEC 60947-2) and 30 kA at 230–240 V AC, so it can handle high-fault downstream of a distribution transformer without upstream coordination headaches. Depth is 73 mm, so it clears most 80 mm-deep enclosures; height is 81 mm. The toggle gives positive ON/OFF indication, and the contact position indicator confirms isolation per IEC 60947-2.","metaTitle":"Schneider Electric C60H2P1AD MCB, 1P+N, 1 A, D Curve, 10 kA","metaDescription":"Schneider Electric C60H2P1AD miniature circuit breaker, 1 A rated, D curve, 10 kA breaking capacity at 440 V AC. Multi9 series, 1P+N, thermal-magnetic, DIN rail mount. Sourced to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Curve code":"D","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"1 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P1AD/miniature-circuit-breaker-c60h-2-poles-1-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P1AD/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C60H2P1AD?","answer":"The C60H2P1AD has a breaking capacity of 10 kA Icu at 440 V AC, 15 kA at 400–415 V AC, and 30 kA at 230–240 V AC, all conforming to IEC 60947-2."},{"question":"What is the D curve and why does it matter?","answer":"The D curve means the magnetic trip activates at 10–14 times the rated current (1 A), so it allows high inrush from motor or transformer loads without nuisance tripping — not ideal for resistive loads."},{"question":"Where can I buy C60H2P1AD?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P1AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P1AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}