{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P20AB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P20AB","canonicalUrl":"https://aoctrl.com/schneider/C60H2P20AB","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P20AB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H2P20AB, Multi9 C60 series, miniature circuit breaker, 1P+N, 20 A rated current, B-curve, 10-30 kA breaking capacity per IEC 60947-2, 36 mm wide, 35 mm DIN rail mount.","salesMarkdown":"The Schneider Electric C60H2P20AB is a 1P+N miniature circuit breaker from the Multi9 C60 series, rated at 20 A with a B-curve trip characteristic (magnetic trip between 3 and 5 times In). It protects a single pole, with the neutral switched and on the left side of the device. The thermal-magnetic trip unit handles overloads and short-circuits in AC distribution circuits. Breaking capacity is 10 kA Icu at 440 V AC, 15 kA at 400-415 V AC, and 30 kA at 230-240 V AC, all per IEC 60947-2. For DC applications on 2 poles, it achieves 25 kA Icu at 125 V DC. Rated operational voltage is 440 V AC, with insulation voltage rated at 500 V AC. Width is 36 mm (4 x 9 mm pitches), depth 73 mm, height 81 mm. Earth-leakage protection requires a separate block (not integrated).","metaTitle":"Schneider Electric C60H2P20AB C60 MCB, 20A B-Curve, 1P+N, 10","metaDescription":"Schneider Electric C60H2P20AB miniature circuit breaker, 20A rated current, B-curve, 1P+N, 10-30kA breaking capacity per IEC 60947-2. Multi9 range, DIN rail mount. Available to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"20 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P20AB/miniature-circuit-breaker-c60h-2-poles-20-a-b-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P20AB/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60H2P20AB and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit a request for quote to confirm availability and current pricing."},{"question":"What is C60H2P20AB's breaking capacity at 230 V?","answer":"30 kA Icu at 230-240 V AC 50/60 Hz per IEC 60947-2, which is the highest rating in its class for this voltage level."},{"question":"What compliance documentation does this brand provide for C60H2P20AB?","answer":"The device carries IEC 60947-2 certification for breaking capacity and isolation suitability. Tropicalisation per IEC 60068-1 and limitation class per IEC 60947-2 are documented. RoHS and REACH compliance are standard for Schneider Electric's Multi9 range, though specific declarations should be confirmed at order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P20AB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P20AB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}