{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P25AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P25AC","canonicalUrl":"https://aoctrl.com/schneider/C60H2P25AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P25AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H2P25AC, Multi9 C60H series, miniature circuit breaker, 1P+N, 25 A, C curve, 10 kA at 440 V AC, 4 modules wide.","salesMarkdown":"The Schneider Electric C60H2P25AC is a 1P+N miniature circuit breaker from the Multi9 C60H range, rated 25 A at 30 °C with a C trip curve (magnetic tripping between 5 and 10 times In). It breaks up to 10 kA Icu at 440 V AC (IEC 60947-2), which is the figure that governs its fault-clearing ability in a 400 V three-phase distribution board; at 230 V it handles 30 kA, so it's comfortable in a main sub-feed position as long as the upstream device limits let-through energy below that. The 1P+N configuration switches the phase and switches the neutral but does not protect the neutral — only the phase pole is protected. It occupies 4 module pitches (36 mm width) on a 35 mm symmetrical DIN rail, so it's a straightforward swap into any Multi9 or similar DIN-rail distribution board. The neutral position is left, which matters when you're laying out busbars or pre-wired neutral links in a distribution board — keep the neutral bar on the left side of the MCB. The toggle gives local ON/OFF indication, and there's a contact position indicator so you can visually confirm the state without relying on the handle position alone. That's a nice safety check for a junior tech doing a panel walk-down. Depth is 73 mm, height 81 mm. That's a standard Multi9 footprint — fits existing enclosures without a gland-plate or cover-depth surprise. Tropicalisation per IEC 60068-1 means it's tested for damp heat, so it's fine in non-conditioned electrical rooms.","metaTitle":"Schneider C60H2P25AC MCB, C Curve 25A 1P+N, 10kA","metaDescription":"Schneider Electric C60H2P25AC miniature circuit breaker, 25A C-curve, 1P+N, 10kA breaking capacity at 440V AC. Multi9 range, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"25 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P25AC/miniature-circuit-breaker-c60h-2-poles-25-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P25AC/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the C60H2P25AC?","answer":"It is a 25 A, C-curve, 1P+N miniature circuit breaker. Breaking capacity is 10 kA Icu at 440 V AC, 15 kA at 400-415 V AC, and 30 kA at 230-240 V AC, all per IEC 60947-2. Magnetic trip is 5-10 x In. It occupies 4 modules (36 mm) on DIN rail."},{"question":"Where can I buy the C60H2P25AC?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time. Submit an RFQ for a firm price and lead time."},{"question":"What compliance documentation does Schneider provide for the C60H2P25AC?","answer":"The MCB is designed to IEC 60947-2, with breaking capacities, insulation voltage (500 V AC), and isolation suitability all certified to that standard. It also carries tropicalisation conforming to IEC 60068-1. For specific RoHS, REACH, or UL documentation, request the compliance package with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P25AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P25AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}