{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P2AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P2AC","canonicalUrl":"https://aoctrl.com/schneider/C60H2P2AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P2AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H series, C60H2P2AC miniature circuit breaker, 2 A rated current, C-curve, 1P+N, 10 kA Icu at 440 V AC, 30 kA Icu at 230 V AC.","salesMarkdown":"The C60H2P2AC is a 2 A, C-curve miniature circuit breaker from the Schneider Multi9 C60H family, single-pole plus neutral (1P+N). The C-curve means magnetic tripping occurs at 5 to 10 times rated current (10 to 20 A), making it a standard choice for general-purpose distribution and moderate inrush loads like lighting or small transformers — not for motor starts or high-surge circuits. The 30 kA Icu at 230 V AC (per IEC 60947-2) is the key fault-clearing number for most residential and light commercial panels; it safely interrupts a short-circuit fault up to 30 kA without welding contacts or cascading upstream. At 440 V AC the breaking capacity drops to 10 kA, which still covers most industrial distribution boards. The 2 A rating at 30 °C ambient is the continuous current the bimetal strip carries without tripping — derate above 30 °C per the thermal curve. ## Deployment context Snaps onto a 35 mm symmetrical DIN rail, occupying 4 module pitches (36 mm width), which is standard for a 1P+N MCB in a distribution board. The tunnel-type terminals accept up to 25 mm² rigid or 16 mm² flexible wire; strip length is 14 mm, tighten to 2 N·m. The toggle handle gives local ON/OFF indication and a contact position indicator shows whether the contacts are actually open or closed, not just the handle position.","metaTitle":"Schneider Electric C60H2P2AC C60H MCB, 2A, C-Curve, 1P+N","metaDescription":"Schneider Electric C60H2P2AC Multi9 C60H miniature circuit breaker, 2 A rated, C-curve, 1P+N, 10 kA breaking capacity at 440 V AC. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"2 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P2AC/miniature-circuit-breaker-c60h-2-poles-2-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P2AC/alternatives.json"},"ai":{"faq":[{"question":"What is C60H2P2AC's breaking capacity at 230 V?","answer":"The C60H2P2AC has a 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2. This is the short-circuit current it can safely interrupt at that voltage."},{"question":"What is the C-curve trip range for this MCB?","answer":"The magnetic tripping limit is 5 to 10 times In, so for the 2 A rating, magnetic trip occurs between 10 A and 20 A. This suits general-purpose distribution and moderate inrush loads."},{"question":"Where can I buy C60H2P2AC and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P2AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P2AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}