{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P32AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P32AD","canonicalUrl":"https://aoctrl.com/schneider/C60H2P32AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P32AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H series, C60H2P32AD miniature circuit breaker, D curve, 32 A, 1P+N, 10-30 kA breaking capacity.","salesMarkdown":"## What this MCB does on a DIN rail The C60H2P32AD is a 1P+N miniature circuit breaker from the Multi9 C60H series, rated 32 A at 40 °C with a D tripping curve. Breaking capacity hits 30 kA at 230–240 V AC and 15 kA at 400–415 V AC, so it handles substantial fault currents in distribution panels. ## D curve — why it matters for motor and transformer circuits Standard B or C curve MCBs can nuisance-trip on the startup surge of a motor or transformer. The D curve's 10–14 x In window lets that inrush pass without opening, while still clearing a hard short. For a 32 A breaker, that means magnetic hold-up to roughly 320–448 A peak before the solenoid fires. Thermal-magnetic trip technology handles the overload side with a bimetal strip. ## Panel integration — what fits where Width is 36 mm (4 x 9 mm pitches). Depth 73 mm, height 81 mm. Tunnel-type terminals accept up to 35 mm² rigid or 25 mm² flexible copper; strip length 14 mm, tighten to 3.5 N·m. Neutral position is left. The toggle gives local ON/OFF indication and a contact position indicator confirms isolation status — it's certified for isolation per IEC 60947-2.","metaTitle":"Schneider Electric C60H2P32AD MCB, D Curve, 32 A, 1P+N","metaDescription":"Schneider Electric C60H2P32AD Multi9 miniature circuit breaker, D curve, 32 A rated current, 1P+N, 10-30 kA breaking capacity, current lifecycle. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Curve code":"D","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"32 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P32AD/miniature-circuit-breaker-c60h-2-poles-32-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P32AD/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60H2P32AD and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to C60H2P32AD in the same family?","answer":"Within the Multi9 C60H series, the C60H2P32AD is the 32 A D-curve 1P+N variant. A C60H2P32B would offer the same current and poles with a B curve for general-purpose loads; a C60H2P32C gives a C curve for moderate inrush. No pin-compatible drop-in exists outside the D curve."},{"question":"What compliance documentation does Schneider provide for C60H2P32AD?","answer":"The breaker carries IEC 60947-2 certification for breaking capacity and isolation suitability. Tropicalisation per IEC 60068-1 is class 2. Limitation class 3 per IEC 60947-2. RoHS/REACH declarations are standard for the Multi9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P32AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P32AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}