{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P40AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P40AC","canonicalUrl":"https://aoctrl.com/schneider/C60H2P40AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P40AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H, C60H2P40AC, miniature circuit breaker, 40 A rated current, C curve, 1P+N, breaking capacity 10 kA at 440 V AC.","salesMarkdown":"The Schneider Electric C60H2P40AC is a Multi9 C60H miniature circuit breaker (MCB) rated at 40 A at 30 °C, with a C curve (magnetic trip at 5 to 10 times In). The thermal-magnetic trip handles overloads and short circuits, and the breaking capacity reaches 30 kA at 230-240 V AC, 15 kA at 400-415 V AC, and 10 kA at 440 V AC (all per IEC 60947-2). ## DIN-rail fit and panel space The breaker occupies 4 modules of 9 mm pitch (36 mm total width), 81 mm tall, 73 mm deep. That 73 mm depth is the dimension to watch when you're laying out a shallow enclosure — it's the body depth, not including the toggle throw. Terminals accept up to 35 mm² rigid or 25 mm² flexible wire; strip length is 14 mm, and the recommended tightening torque is 3.5 N·m. The tunnel-type terminals are the standard cage-clamp style, so a good screwdriver with a parallel tip (not a pozi) seats the conductor cleanly. The C curve (5-10 x In) means the magnetic trip kicks in between 200 A and 400 A. That's the standard curve for general-purpose distribution — lighting, socket outlets, small motor circuits where inrush isn't extreme. The limitation class is 3 per IEC 60947-2, which limits let-through energy — important for downstream cable protection.","metaTitle":"Schneider Electric C60H2P40AC C60H MCB, 40 A, C Curve, 1P+N","metaDescription":"Schneider Electric C60H2P40AC Multi9 C60H miniature circuit breaker, 40 A rated current, C curve, 1P+N, 10-30 kA breaking capacity. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"40 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P40AC/miniature-circuit-breaker-c60h-2-poles-40-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P40AC/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for C60H2P40AC?","answer":"Submit an RFQ through your preferred independent distribution channel. Availability and current pricing are confirmed at quote time — no stock count or price is listed here, but the part is sourced to order."},{"question":"What is the closest alternative to C60H2P40AC in the same family?","answer":"Within the Multi9 C60 range, the C60H2P40AC is a 1P+N, 40 A, C curve unit. If you need a 2-pole (2P) version with the same rating and curve, look at the C60H2P40 (2P, no switched neutral). The footprint changes to 2 modules wide instead of 4, so verify DIN-rail space before swapping."},{"question":"What is C60H2P40AC's listed depth?","answer":"The depth is 73 mm, measured from the DIN-rail mounting surface to the front of the toggle. That's the body depth — add clearance for wire bending and the toggle throw."},{"question":"What is C60H2P40AC's listed range?","answer":"It belongs to the Multi9 range, which is Schneider Electric's family of miniature circuit breakers and residual current devices for distribution panels."},{"question":"What compliance documentation does this brand provide for C60H2P40AC?","answer":"The breaker is designed to IEC 60947-2 and IEC 60068-1 (tropicalisation class 2). It carries ON/OFF indication and a contact position indicator. For specific certifications (UL, CSA, CE, RoHS, REACH), refer to the manufacturer's declaration of conformity — that documentation is available from Schneider Electric's support portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P40AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P40AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}