{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P40AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P40AD","canonicalUrl":"https://aoctrl.com/schneider/C60H2P40AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P40AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60 series, C60H2P40AD miniature circuit breaker, 1P+N, 40 A rated current, D curve, thermal-magnetic trip, 10-30 kA breaking capacity.","salesMarkdown":"The C60H2P40AD is a Schneider Electric Multi9 C60-series miniature circuit breaker — a 1P+N thermal-magnetic MCB rated 40 A at 40 °C with a D tripping curve. The 1P+N pole arrangement protects one phase and switches the neutral; the neutral pole is not protected, so this is a distribution MCB, not a main isolator for a 2-pole load. Breaking capacity runs 30 kA at 230–240 V AC, 15 kA at 400–415 V AC, and 10 kA at 440 V AC — the 10 kA at 440 V is the limiting figure for a 400 V line-to-line feed. The 15 kA at 400–415 V gives headroom above the typical 10 kA utility fault level in most commercial panels. The 36 mm width at 4 module pitches occupies four 9 mm slots, so plan for 4 × 9 = 36 mm of rail space per unit. Depth is 73 mm, height 81 mm. Tunnel-type terminals accept up to 35 mm² rigid or 25 mm² flexible; strip 14 mm and torque to 3.5 N·m. The neutral position is left. Toggle control with ON/OFF indication and a contact position indicator.","metaTitle":"Schneider Electric C60H2P40AD C60 MCB, 1P+N, 40 A, D Curve","metaDescription":"Schneider Electric C60H2P40AD Multi9 miniature circuit breaker. 40 A rated current, D curve, 1P+N, 10-30 kA breaking capacity. Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Curve code":"D","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"40 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P40AD/miniature-circuit-breaker-c60h-2-poles-40-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P40AD/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the C60H2P40AD and get a price?","answer":"The C60H2P40AD is sourced to order against an RFQ through independent distribution channels. Submit a request for quote (RFQ) to confirm current availability and pricing — no stock or price figures are published here."},{"question":"What does the D curve mean on this breaker?","answer":"The D curve sets the magnetic trip threshold at 10–14× the rated current, so for a 40 A breaker, instantaneous trip occurs between 400 A and 560 A. This is designed for loads with high inrush, such as small motors, transformers, or welding equipment, where a B or C curve would trip on startup."},{"question":"What compliance documentation does the C60H2P40AD carry?","answer":"The breaker is certified to IEC 60947-2 and IEC 60068-1 for tropicalisation. It is suitable for isolation per IEC 60947-2. The evidence does not list UL, CSA, RoHS, or REACH declarations — confirm with the supplier at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P40AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P40AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}