{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P63AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P63AD","canonicalUrl":"https://aoctrl.com/schneider/C60H2P63AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P63AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H, C60H2P63AD, miniature circuit-breaker, 2P, 63 A, D-curve, 10 kA breaking capacity, DIN-rail mount.","salesMarkdown":"The Schneider Electric C60H2P63AD is a Multi9 C60H miniature circuit-breaker, 2-pole, rated 63 A at 40 °C with a D-curve magnetic trip of 10 to 14 times In. It carries a 10 kA Icn breaking capacity at 230/400 V AC per EN 60898, and higher Icu ratings per IEC 60947-2 — up to 30 kA at 230-240 V AC and 25 kA at 125 V DC (2P). That dual-standard rating means it qualifies for both residential-distribution boards (EN 60898) and industrial panel applications (IEC 60947-2), so the same part covers the spec for either install. But the IEC 60947-2 ratings are where this breaker earns its keep in industrial panels: 30 kA Icu at 230-240 V AC and 15 kA at 400-415 V AC. The D-curve (10-14x In) is sized for transformer inrush, motor starting, or welding loads — it won't nuisance-trip on a 3-4x startup surge that a C-curve would catch. The 73 mm depth leaves clearance in most shallow enclosures.","metaTitle":"Schneider Electric C60H2P63AD MCB, D-Curve 63A 2P, Multi9 Se","metaDescription":"Schneider Electric C60H2P63AD miniature circuit breaker, 63A rated, D-curve, 2-pole, 10kA breaking capacity. Sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Standards":"IEC 60947-2 EN 60898","Curve code":"D","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC DC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m upside 3.5 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"63 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"12...440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P63AD/miniature-circuit-breaker-c60h-2-poles-63-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P63AD/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C60H2P63AD?","answer":"It carries a 10 kA Icn at 230/400 V AC per EN 60898, and up to 30 kA Icu at 230-240 V AC per IEC 60947-2. DC ratings reach 25 kA at 125 V DC (2P) and 40 kA at 125 V DC (3P)."},{"question":"What does the D-curve mean on this breaker?","answer":"The D-curve trips magnetically at 10 to 14 times the rated current (In), so a 63 A breaker holds up to about 630-882 A instantaneous trip threshold. That suits loads with high inrush like small transformers, motor starters, or welding equipment."},{"question":"Where can I buy C60H2P63AD?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P63AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P63AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}