{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H2P6AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H2P6AD","canonicalUrl":"https://aoctrl.com/schneider/C60H2P6AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H2P6AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H Miniature Circuit-Breaker, 1P+N, 6 A, D curve, 10 kA breaking capacity at 440 V AC.","salesMarkdown":"The Schneider Electric C60H2P6AD is a thermal-magnetic miniature circuit-breaker from the Multi9 C60 range, 1P+N configuration, rated 6 A at 40 °C with a D tripping curve (magnetic trip at 10–14 × In). It protects branch circuits against overload and short-circuit faults in AC distribution panels. Breaking capacity: 10 kA Icu at 440 V AC (IEC 60947-2), with higher ratings at lower voltages — 30 kA at 230–240 V AC, 15 kA at 400–415 V AC, and 25 kA at 125 V DC (2P). D curve magnetic trip operates at 10–14 × In. This suits loads with high inrush, such as small motors or transformers. Rated operational voltage 440 V AC, insulation voltage 500 V AC. Width is 36 mm (4 × 9 mm pitches). Depth 73 mm, height 81 mm. Strip length 14 mm.","metaTitle":"C60H2P6AD Miniature Circuit-Breaker, 6 A, Curve D, 1P+N, Mul","metaDescription":"Schneider Electric C60H2P6AD Miniature Circuit-Breaker, 6 A rated current, D curve, 1P+N, 10 kA breaking capacity at 440 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Height":"81 mm","Curve code":"D","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"6 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H2P6AD/miniature-circuit-breaker-c60h-2-poles-6-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H2P6AD/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H2P6AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H2P6AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}