{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H3P50AB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H3P50AB","canonicalUrl":"https://aoctrl.com/schneider/C60H3P50AB","factsUrl":"https://aoctrl.com/api/mcp/products/C60H3P50AB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H, C60H3P50AB, miniature circuit breaker, 3P, 50 A, B curve, 10-40 kA breaking capacity, DIN rail mount.","salesMarkdown":"The C60H3P50AB is a 3-pole miniature circuit breaker from the Schneider Electric Multi9 C60H series, rated 50 A at 30 °C with a B tripping curve (3–5 × In magnetic trip). Breaking capacity varies by voltage: 30 kA Icu at 230–240 V AC, 15 kA at 400–415 V AC, and 10 kA at 440 V AC, all per IEC 60947-2. Rated operational voltage is 440 V AC, insulation voltage 500 V AC. The 3 protected poles handle three-phase distribution (, L2, L3) with a separate earth-leakage block if needed. Isolation capability is confirmed per IEC 60947-2 — the toggle provides visible ON/OFF indication and a contact position indicator. Width is 54 mm (6 × 9 mm pitches), depth 73 mm, height 81 mm — occupies 3 standard module spaces. Tunnel-type terminals accept up to 35 mm² rigid or 25 mm² flexible cable; strip length 14 mm, tightening torque 3.5 N·m. Limitation class 3 per IEC 60947-2 limits let-through energy, helping downstream coordination.","metaTitle":"Schneider Electric C60H3P50AB MCB, 50A B Curve, 3P, Multi9","metaDescription":"Schneider Electric C60H3P50AB miniature circuit breaker, 50 A rated current, B curve, 3 poles, 10-40 kA breaking capacity per IEC 60947-2. DIN rail mount. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Curve code":"B","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"50 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H3P50AB/miniature-circuit-breaker-c60h-3-poles-50-a-b-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H3P50AB/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60H3P50AB and how do I get a price?","answer":"The C60H3P50AB is available to order through independent distribution. Submit an RFQ to confirm current pricing and availability — no stock count or price is published here."},{"question":"What is the breaking capacity of C60H3P50AB at 400 V?","answer":"At 400–415 V AC, the C60H3P50AB has a rated ultimate breaking capacity (Icu) of 15 kA and a service breaking capacity (Ics) of 15 kA, both per IEC 60947-2."},{"question":"What compliance documentation does this brand provide for C60H3P50AB?","answer":"The C60H3P50AB is designed to IEC 60947-2 (breaking capacity, isolation, limitation class) and IEC 60068-1 (tropicalisation). It carries the Schneider Electric Multi9 brand approvals — typically UL, CSA, CE, and UKCA, though specific marks should be verified against the unit's label."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H3P50AB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H3P50AB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}