{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H3P50AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H3P50AC","canonicalUrl":"https://aoctrl.com/schneider/C60H3P50AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H3P50AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60, C60H3P50AC, 3-pole miniature circuit breaker, 50 A rated, C-curve, 10 kA breaking capacity at 440 V AC.","salesMarkdown":"## What this MCB does in the panel The Schneider Electric C60H3P50AC is a 3-pole C60H miniature circuit breaker rated 50 A at 30 °C, with a C-curve trip characteristic (magnetic tripping between 5 and 10 times In). At 230…240 V AC the C60H3P50AC interrupts 30 kA; at 400…415 V AC it handles 15 kA; at its rated operational voltage of 440 V AC it breaks 10 kA. All figures are Icu per IEC 60947-2, so the standard certifies the breaker can make and break a fault once at that level and still be serviceable. The thermal-magnetic trip unit handles overloads via a bimetal strip (thermal) and short-circuits via a solenoid (magnetic). The C-curve means the magnetic trip fires between 5× and 10× In — 250 A to 500 A for this 50 A unit — which suits lighting, distribution, and general-purpose loads where inrush is moderate but not as high as motor-start. The ON/OFF toggle gives local indication, and a contact position indicator confirms the main contacts are open — IEC 60947-2 certified for isolation when the handle is in the OFF position. Tropicalisation level 2 per IEC 60068-1, limitation class 3 per IEC 60947-2. Operating temperature range -25…60 °C, storage -40…70 °C. Relative humidity 95% at 55 °C. Altitude limit 2000 m. The MCB carries IEC 60947-2 certification for the breaking capacity and isolation claims listed above.","metaTitle":"Schneider C60H3P50AC MCB, 50A 3P C-Curve, 10kA","metaDescription":"Schneider Electric C60H3P50AC miniature circuit breaker, 50A, 3-pole, C-curve, 10 kA breaking capacity at 440 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"50 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H3P50AC/miniature-circuit-breaker-c60h-3-poles-50-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H3P50AC/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60H3P50AC?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of C60H3P50AC at 400 V?","answer":"At 400…415 V AC 50/60 Hz the C60H3P50AC has a rated ultimate breaking capacity (Icu) of 15 kA per IEC 60947-2."},{"question":"What does the C-curve mean on this MCB?","answer":"The C-curve means the magnetic trip operates between 5 and 10 times the rated current (250–500 A for this 50 A unit), which suits general-purpose distribution and lighting loads with moderate inrush."},{"question":"What compliance documentation does this brand provide for C60H3P50AC?","answer":"The MCB is certified to IEC 60947-2 for breaking capacity and isolation. Tropicalisation conforms to IEC 60068-1. RoHS and REACH compliance documentation is available through the standard Schneider Electric channels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H3P50AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H3P50AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}