{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H3P50AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H3P50AD","canonicalUrl":"https://aoctrl.com/schneider/C60H3P50AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H3P50AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, Multi9 series, C60H3P50AD miniature circuit breaker, 3-pole, 50 A, D curve, 10-14 x In magnetic trip, 10 kA Icu at 440 V AC.","salesMarkdown":"The Schneider Electric C60H3P50AD is a 3-pole C60H miniature circuit breaker from the Multi9 range, rated 50 A at 40 °C with a D trip curve. The D curve's magnetic tripping limit of 10...14 x In means it handles high inrush loads — motor starting, transformer energization, or welding equipment — without nuisance tripping on the magnetic element, while still clearing hard faults. Breaking capacity is 10 kA Icu at 440 V AC (IEC 60947-2), with higher ratings at lower voltages: 30 kA at 230...240 V AC and 25 kA at 125 V DC (2P). For distribution panels feeding motor control centers or general branch circuits, this gives solid fault-clearing headroom. Fixed mounting, tunnel-type terminals accept up to 35 mm² rigid or 25 mm² flexible wire; strip length 14 mm, torque to 3.5 N·m. The 6-pitch (54 mm wide) footprint fits a standard 3-pole MCB slot.","metaTitle":"Schneider C60H3P50AD C60 MCB, 3P, 50 A, D Curve, 10-14x In","metaDescription":"Schneider Electric C60H3P50AD miniature circuit breaker, 3-pole, 50 A, D curve, 10-14x In magnetic trip. 10 kA Icu at 440 V AC. DIN rail mount. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"50 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H3P50AD/miniature-circuit-breaker-c60h-3-poles-50-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H3P50AD/alternatives.json"},"ai":{"faq":[{"question":"What is the C60H3P50AD rated current and trip curve?","answer":"Rated 50 A at 40 °C with a D curve. The magnetic trip operates at 10...14 x In (500...700 A), designed for high-inrush loads like motors and transformers."},{"question":"What is the breaking capacity of the C60H3P50AD?","answer":"10 kA Icu at 440 V AC per IEC 60947-2. At 230...240 V AC it rises to 30 kA Icu. The Ics service breaking capacity is 15 kA at 440 V AC, allowing reclosure after a fault at that level."},{"question":"Where can I buy the C60H3P50AD and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What compliance documentation is available for the C60H3P50AD?","answer":"The breaker carries IEC 60947-2 certification for breaking capacity and isolation suitability. Tropicalisation per IEC 60068-1 (class 2) and limitation class 3 per IEC 60947-2 are specified. RoHS and REACH compliance documentation is typically available from Schneider Electric upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H3P50AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H3P50AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}