{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H3P63AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H3P63AD","canonicalUrl":"https://aoctrl.com/schneider/C60H3P63AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H3P63AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H, C60H3P63AD, miniature circuit breaker, 63 A, D curve, 3 poles, 30 kA breaking capacity at 230-240 V AC.","salesMarkdown":"## What this MCB does and where it fits The Schneider Electric C60H3P63AD is a C60H-series miniature circuit breaker from the Multi9 range, rated 63 A at 40 °C with a D tripping curve (magnetic trip threshold 10–14 × In). ## Breaking capacity and what it means for your panel The C60H3P63AD delivers 30 kA Icu at 230–240 V AC and 15 kA Icu at 400–415 V AC, both per IEC 60947-2. For a panel fed by a transformer with a high short-circuit rating, this breaker stays within its interrupting envelope without needing a current-limiting upstream fuse. Snaps onto 35 mm DIN rail — 6 module pitches (9 mm each) wide, 54 mm total width, 81 mm tall, 73 mm deep. The toggle gives ON/OFF indication, and there's a contact position indicator for isolation verification (suitable for isolation per IEC 60947-2). Earth-leakage protection is handled by a separate block, not integrated.","metaTitle":"Schneider Electric C60H3P63AD C60H MCB, 63 A, D Curve, 3P","metaDescription":"Schneider Electric C60H3P63AD miniature circuit breaker, 63 A rated current, D curve, 3 poles, 10-14 x In magnetic trip. Breaking capacity 30 kA at 230-240 V AC. Current lifecycle","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"63 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H3P63AD/miniature-circuit-breaker-c60h-3-poles-63-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H3P63AD/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C60H3P63AD at 230 V?","answer":"30 kA Icu at 230–240 V AC 50/60 Hz per IEC 60947-2. At 400–415 V AC it's 15 kA Icu."},{"question":"What wire sizes does the C60H3P63AD accept?","answer":"Tunnel terminals accept up to 35 mm² rigid or 25 mm² flexible copper. Strip length is 14 mm, torque to 3.5 N·m."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H3P63AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H3P63AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}