{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H3P6AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H3P6AC","canonicalUrl":"https://aoctrl.com/schneider/C60H3P6AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H3P6AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H3P6AC, Multi9 C60 series, miniature circuit breaker, 3 poles, 6 A, C curve, 10-40 kA breaking capacity, 73 mm depth.","salesMarkdown":"The C60H3P6AC is a 3-pole miniature circuit breaker from the Multi9 C60 range, rated 6 A at 30 °C with a C curve (magnetic tripping between 5 and 10 times In). The 6 A rating suits branch circuits with a connected load around 1.4 kW on a 230 V line or 2.5 kW on 400 V three-phase. The C60H3P6AC carries 30 kA Icu at 230–240 V AC, 15 kA at 400–415 V, and 10 kA at 440 V — all per IEC 60947-2. The thermal-magnetic trip unit combines a bimetal strip for overload protection (time-delayed, inversely proportional to current) and a solenoid for short-circuit protection (instantaneous above the magnetic threshold). At 54 mm wide (6 × 9 mm pitches), it occupies three pole positions on the rail. Depth of 73 mm and height of 81 mm leave clearance for wiring ducts and gland plates; check the enclosure depth if using a shallow 80 mm box. The toggle actuator provides ON/OFF indication and local manual switching.","metaTitle":"Schneider Electric C60H3P6AC C60 MCB, 6 A, C Curve, 3P, 10-4","metaDescription":"Schneider Electric C60H3P6AC miniature circuit breaker, 6 A rated current, C curve, 3 poles, 10-40 kA breaking capacity per IEC 60947-2. Multi9 range. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"6 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"15 kA conforming to IEC 60947-2 - 12...440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 60 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H3P6AC/miniature-circuit-breaker-c60h-3-poles-6-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H3P6AC/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the C60H3P6AC at 400 V?","answer":"At 400–415 V AC, the rated ultimate breaking capacity (Icu) is 15 kA per IEC 60947-2. At 440 V it drops to 10 kA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H3P6AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H3P6AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}