{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H4P16AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H4P16AC","canonicalUrl":"https://aoctrl.com/schneider/C60H4P16AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H4P16AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H series, C60H4P16AC, 4-pole miniature circuit breaker, C-curve, 16 A rated current, 10 kA breaking capacity at 230/400 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The Schneider Electric C60H4P16AC is a 4-pole miniature circuit breaker from the Multi9 C60H series, rated at 16 A with a C-curve trip characteristic (magnetic tripping between 5 and 10 times In). It is a thermal-magnetic MCB designed for distribution applications, providing overcurrent and short-circuit protection in final subcircuits. The 16 A rating at 30 °C sets the continuous current capacity; derate for higher ambient temperatures per the thermal curve. The C60H4P16AC delivers 10 kA Icn at 230/400 V AC per EN 60898, and under IEC 60947-2 it achieves 15 kA Icu at 400–415 V AC and 30 kA Icu at 230–240 V AC. The service breaking capacity (Ics) is 7.5 kA at 230/400 V AC per EN 60898, meaning after clearing a fault at that level the breaker remains functional. For DC circuits, it handles 25 kA at 125 V DC (2-pole series) and 50 kA at 250 V DC (4-pole series). These figures give the panel designer room for selectivity coordination downstream. A 16 A C-curve breaker with 10 kA Icn at 230/400 V AC will typically coordinate with a larger upstream device rated above that level, provided the let-through energy is managed. The limitation class is 3 per IEC 60947-2, which limits peak let-through current and energy — helpful for protecting downstream components. The 4-pole body occupies 72 mm width (8 modules of 9 mm pitch), so plan for 8 DIN spaces in the distribution board. Depth is 73 mm, height 81 mm. The toggle switch provides local ON/OFF indication with a contact position indicator. Earth-leakage protection requires a separate block — not integrated.","metaTitle":"Schneider Electric C60H4P16AC MCB, 4P C-Curve 16 A, 10 kA","metaDescription":"Schneider Electric C60H4P16AC miniature circuit breaker, 4-pole, C-curve, 16 A rated current. Breaking capacity 10 kA Icn at 230/400 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN 60898 IEC 60947-2","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 2 N.m upside 2 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"16 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"60 V DC per pole","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H4P16AC/miniature-circuit-breaker-c60h-4-poles-16-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H4P16AC/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60H4P16AC and how do I get a price?","answer":"The C60H4P16AC is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing."},{"question":"What is the breaking capacity of C60H4P16AC?","answer":"The C60H4P16AC has a breaking capacity of 10 kA Icn at 230/400 V AC per EN 60898, and up to 15 kA Icu at 400–415 V AC per IEC 60947-2. For DC, it achieves 25 kA at 125 V DC (2-pole series) and 50 kA at 250 V DC (4-pole series)."},{"question":"What compliance documentation does this brand provide for C60H4P16AC?","answer":"The C60H4P16AC is certified to EN 60898 and IEC 60947-2. It also carries tropicalisation treatment per IEC 60068-1 and suitability for isolation per IEC 60947-2. For specific RoHS, REACH, or UL documentation, contact the supplier at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H4P16AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H4P16AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}