{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H4P25AB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H4P25AB","canonicalUrl":"https://aoctrl.com/schneider/C60H4P25AB","factsUrl":"https://aoctrl.com/api/mcp/products/C60H4P25AB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60 series, Multi9 range, C60H4P25AB miniature circuit breaker, 4-pole, 25 A, Curve B, 10 kA Icn at 230/400 V AC.","salesMarkdown":"Under IEC 60947-2, the ultimate breaking capacity (Icu) reaches 15 kA at 400–415 V AC and 30 kA at 230–240 V AC. For DC applications, the Icu is 25 kA at 125 V DC (2-pole series) and 40 kA at 125 V DC (3-pole series). These figures let the panel designer coordinate selectivity with upstream devices — the 15 kA Icu at 400 V is the figure to match against the main breaker's let-through. The 4-pole footprint occupies 8 modules of 9 mm pitch, yielding a total width of 72 mm, depth of 73 mm, and height of 81 mm. The toggle actuator provides local ON/OFF indication and a contact position indicator confirms isolation status — the breaker is suitability for isolation certified per IEC 60947-2.","metaTitle":"Schneider Electric C60H4P25AB C60 MCB, 25 A, 4P, Curve B, 10","metaDescription":"Schneider Electric C60H4P25AB C60 series MCB, 25 A rated, 4-pole, Curve B, 10 kA Icn at 230/400 V AC. Certified to EN 60898 and IEC 60947-2. Active lifecycle. Quoted to order again","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN 60898 IEC 60947-2","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 2 N.m upside 2 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"25 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"12...440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H4P25AB/miniature-circuit-breaker-c60h-4-poles-25-a-b-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H4P25AB/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for C60H4P25AB?","answer":"Submit an RFQ through the storefront. Pricing and current stock levels are confirmed at quote time through independent distribution channels."},{"question":"What are the key ratings of C60H4P25AB?","answer":"Rated 25 A at 30 °C, 4-pole, Curve B (3–5 x In magnetic trip), with 10 kA Icn at 230/400 V AC. Certified to EN 60898 and IEC 60947-2."},{"question":"What is the depth of C60H4P25AB?","answer":"The depth is 73 mm. Overall dimensions: 72 mm wide (8 modules of 9 mm pitch) by 81 mm high."},{"question":"What compliance documentation does Schneider Electric provide for C60H4P25AB?","answer":"The breaker is certified to EN 60898 and IEC 60947-2, tropicalised per IEC 60068-1 Class 2, and carries a limitation class of 3 per IEC 60947-2. It is suitability for isolation certified per IEC 60947-2. Standard RoHS/REACH declarations are available from the manufacturer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H4P25AB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H4P25AB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}