{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H4P32AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H4P32AC","canonicalUrl":"https://aoctrl.com/schneider/C60H4P32AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H4P32AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H, C60H4P32AC, miniature circuit breaker, 4-pole, C-curve, 32 A rated current, 10 kA breaking capacity per EN 60898, thermal-magnetic trip unit, 35 mm DIN rail mount.","salesMarkdown":"The C60H4P32AC is a 4-pole miniature circuit breaker from Schneider Electric's Multi9 C60 range, rated 32 A at 30 °C with a C-curve magnetic trip (5 to 10 x In). The 10 kA Icn at 230/400 V AC per EN 60898 is the rated short-circuit capacity for the breaker under standard conditions; the higher Icu values (up to 30 kA at 230–240 V AC per IEC 60947-2) cover industrial fault levels. For a 4-pole breaker, the 32 A rating and C-curve suit sub-distribution boards where the downstream load includes small motors, lighting, and socket outlets. The thermal-magnetic trip unit combines a bimetal element for overload protection and a solenoid for short-circuit response. The magnetic threshold at 5–10 x In means the breaker holds through transformer inrush and motor starting current without nuisance tripping, but clears fast on a hard fault. The toggle control provides local ON/OFF indication and a contact position indicator confirms the state of the moving contacts for isolation verification. The tropicalisation treatment (class 2 per IEC 60068-1) and 95 % relative humidity rating at 55 °C make it suitable for unconditioned electrical rooms and outdoor-rated enclosures in humid climates. Compliance documentation includes EN 60898 (household and similar installations) and IEC 60947-2 (industrial) standards. The limitation class 3 per IEC 60947-2 indicates energy-limiting performance that reduces let-through energy on faults.","metaTitle":"Schneider C60H4P32AC MCB, C-Curve 32A 4P, 10kA","metaDescription":"Schneider Electric C60H4P32AC miniature circuit breaker, 32A C-curve 4-pole, 10kA breaking capacity per EN 60898. DIN-rail mount, thermal-magnetic trip. Sourced to order against RF","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN 60898 IEC 60947-2","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m upside 3.5 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"32 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"12...440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H4P32AC/miniature-circuit-breaker-c60h-4-poles-32-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H4P32AC/alternatives.json"},"ai":{"faq":[{"question":"What is C60H4P32AC's listed depth (73 mm) on this component line?","answer":"The depth is 73 mm, with a width of 72 mm (8 x 9 mm pitches) and height of 81 mm. These dimensions fit standard 100 mm deep enclosures on a 35 mm DIN rail."},{"question":"What compliance documentation does this brand provide for C60H4P32AC (RoHS, REACH, UL, IEC)?","answer":"The breaker is certified to EN 60898 and IEC 60947-2. It is suitable for isolation per IEC 60947-2, with a rated insulation voltage of 500 V AC. The evidence does not list RoHS, REACH, or UL specifically, but the IEC standards cover the core safety and performance requirements for distribution circuit breakers."},{"question":"Who supplies C60H4P32AC and how is it quoted for volume purchases?","answer":"The C60H4P32AC is sourced to order against an RFQ through independent distribution channels. Volume pricing and lead time are confirmed at quote time — submit an RFQ for current availability and pricing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H4P32AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H4P32AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}