{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H4P3AC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H4P3AC","canonicalUrl":"https://aoctrl.com/schneider/C60H4P3AC","factsUrl":"https://aoctrl.com/api/mcp/products/C60H4P3AC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H, miniature circuit breaker, C60H4P3AC, 4P, 3 A, C-curve, 10 kA Icn at 230/400 V AC, 35 mm DIN rail.","salesMarkdown":"The Schneider Electric C60H4P3AC is a 4-pole miniature circuit breaker from the Multi9 C60 range, rated 3 A with a C-curve trip characteristic (5...10 x In magnetic tripping limit). It carries a 10 kA Icn breaking capacity at 230/400 V AC per EN 60898, and higher Icu ratings under IEC 60947-2 — up to 50 kA at 250 V DC for the 4P configuration. The thermal-magnetic trip unit protects distribution circuits in commercial and industrial panels. Occupies 8 x 9 mm pitches (72 mm wide, 81 mm tall, 73 mm deep). The toggle handle provides local ON/OFF indication and a contact position indicator confirms isolation status per IEC 60947-2. ## Breaking capacity and duty ratings The C-curve (5...10 x In) suits mixed resistive and inductive loads where moderate inrush is expected — typical for distribution sub-circuits feeding contactor coils, small motors, or lighting banks. The 10 kA Icn at 230/400 V AC meets EN 60898 for domestic/commercial installations; the IEC 60947-2 Icu ratings extend to 15 kA at 400...415 V AC and 30 kA at 230...240 V AC. For DC applications, the 4P series connection yields 40 kA Icu at 125 V DC and 50 kA at 250 V DC. The Ics (service breaking capacity) is 7.5 kA at 230/400 V AC per EN 60898, meaning the breaker can be reclosed after clearing a fault at that level without replacement.","metaTitle":"Schneider Electric C60H4P3AC MCB, C-Curve 3A 4P, 10 kA","metaDescription":"Schneider Electric C60H4P3AC miniature circuit breaker, Multi9 range, C-curve, 3 A, 4 poles, 10 kA breaking capacity. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"IEC 60947-2 EN 60898","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 2 N.m upside 2 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"3 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"12...440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H4P3AC/miniature-circuit-breaker-c60h-4-poles-3-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H4P3AC/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60H4P3AC and how do I get a price?","answer":"The C60H4P3AC is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing."},{"question":"What is C60H4P3AC's listed depth?","answer":"The depth is 73 mm. Combined with the 72 mm width and 81 mm height, it occupies 8 x 9 mm DIN-rail pitches."},{"question":"What is C60H4P3AC's listed range?","answer":"It belongs to the Multi9 range, specifically the C60 product family with the device short name C60H."},{"question":"What compliance documentation does this brand provide for C60H4P3AC?","answer":"The breaker is certified to IEC 60947-2 and EN 60898. It carries tropicalisation class 2 per IEC 60068-1 and limitation class 3 per IEC 60947-2. The suitability for isolation is confirmed per IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H4P3AC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H4P3AC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}