{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H4P50AB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H4P50AB","canonicalUrl":"https://aoctrl.com/schneider/C60H4P50AB","factsUrl":"https://aoctrl.com/api/mcp/products/C60H4P50AB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H series, C60H4P50AB, 4-pole miniature circuit breaker, 50 A rated current, B-curve, 10 kA breaking capacity per EN 60898.","salesMarkdown":"The Schneider Electric C60H4P50AB is a 4-pole miniature circuit breaker from the Multi9 C60H range, rated at 50 A with a B-curve trip characteristic. But under IEC 60947-2, the ultimate breaking capacity (Icu) climbs: 15 kA at 400–415 V AC, 30 kA at 230–240 V AC, and even 50 kA at 250 V DC for the 4-pole configuration. That means the same device can handle a much tougher fault on a 240 V panel or a DC bus than its EN 60898 label suggests — useful if you're spec'ing for a mixed AC/DC installation and want one part number across both. Fixed mounting on a 35 mm DIN rail, 4-pole wide at 72 mm (8 x 9 mm pitches). Rated for operation from -25 °C to 60 °C, storage from -40 °C to 70 °C, and 95 % relative humidity at 55 °C. Complies with both EN 60898 (household-type MCB standard) and IEC 60947-2 (industrial breaker standard), so it's accepted across residential, commercial, and light industrial panels.","metaTitle":"Schneider Electric C60H4P50AB C60H MCB, 50A 4P B-curve, 10kA","metaDescription":"Schneider Electric C60H4P50AB C60H miniature circuit breaker, 50A, 4-pole, B-curve, 10kA breaking capacity. Active production. Quoted to order. EN 60898 / IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN 60898 IEC 60947-2","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m upside 3.5 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"50 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"12...440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H4P50AB/miniature-circuit-breaker-c60h-4-poles-50-a-b-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H4P50AB/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the C60H4P50AB?","answer":"The C60H4P50AB has a 10 kA Icn at 230/400 V AC per EN 60898, and up to 30 kA Icu at 230–240 V AC per IEC 60947-2. For DC applications, it achieves 50 kA Icu at 250 V DC in 4-pole configuration."},{"question":"Where can I buy the C60H4P50AB?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What standards does the C60H4P50AB comply with?","answer":"It complies with EN 60898 and IEC 60947-2, covering both household-type and industrial breaker applications."},{"question":"Does the C60H4P50AB fit on a standard DIN rail?","answer":"Yes, it mounts on a 35 mm symmetrical DIN rail and occupies 72 mm (4 modules) of panel width."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H4P50AB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H4P50AB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}