{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H4P63AB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H4P63AB","canonicalUrl":"https://aoctrl.com/schneider/C60H4P63AB","factsUrl":"https://aoctrl.com/api/mcp/products/C60H4P63AB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H series, C60H4P63AB, 4-pole miniature circuit breaker, B-curve, 63 A, thermal-magnetic, 10 kA breaking capacity, DIN rail mount.","salesMarkdown":"The Schneider Electric C60H4P63AB is a 4-pole miniature circuit breaker from the Multi9 C60H series, rated at 63 A with a B-curve trip characteristic (3–5 × In magnetic tripping limit). It occupies 8 × 9 mm pitches on a 35 mm symmetrical DIN rail, so it takes 72 mm of rail width in the enclosure. The B-curve magnetic trip activates between 3 and 5 times the rated current. That suits resistive and general-purpose loads with modest inrush. Dual-certified to IEC 60947-2 and EN 60898, this breaker carries a 10 kA Icn at 230/400 V AC under EN 60898 and a range of Icu values under IEC 60947-2: 15 kA at 400–415 V AC, 30 kA at 230–240 V AC, and 25 kA at 125 V DC (2-pole series connection). The Ics service breaking capacity sits at 7.5 kA for the 230/400 V AC EN 60898 case — meaning after clearing a fault at that level the breaker remains functional, not just safe. The thermal-magnetic trip unit handles overloads thermally and short-circuits magnetically. Rated insulation voltage is 500 V AC, and the operational voltage range covers 12–440 V AC 50/60 Hz. ## Integration notes The toggle provides local ON/OFF indication, and the contact position indicator confirms isolation visually. Maximum operating altitude is 2000 m without derating.","metaTitle":"Schneider Electric C60H4P63AB Miniature Circuit Breaker, 63","metaDescription":"Schneider Electric C60H4P63AB Multi9 C60H miniature circuit breaker, 63 A rated current, B-curve, 4-pole, 10 kA breaking capacity. Certified to IEC 60947-2 and EN 60898. Available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"IEC 60947-2 EN 60898","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m upside 3.5 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"63 A at 30 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"12...440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H4P63AB/miniature-circuit-breaker-c60h-4-poles-63-a-b-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H4P63AB/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C60H4P63AB?","answer":"The C60H4P63AB carries a 10 kA Icn at 230/400 V AC per EN 60898, and under IEC 60947-2 it achieves up to 30 kA Icu at 230–240 V AC and 15 kA Icu at 400–415 V AC. DC ratings reach 25 kA at 125 V DC (2-pole) and 40 kA at 125 V DC (3-pole)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H4P63AB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H4P63AB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}