{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60H4P6AD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60H4P6AD","canonicalUrl":"https://aoctrl.com/schneider/C60H4P6AD","factsUrl":"https://aoctrl.com/api/mcp/products/C60H4P6AD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H, miniature circuit breaker, C60H4P6AD, 4P, 6 A, D curve, 10 kA Icn at 230/400 V AC, thermal-magnetic trip, 35 mm DIN rail mount.","salesMarkdown":"The Schneider Electric C60H4P6AD is a 4-pole miniature circuit breaker from the Multi9 C60 range, rated at 6 A with a D trip curve. Thermal-magnetic trip technology gives you both overload protection (thermal bimetal) and short-circuit protection (magnetic coil) in one unit. Breaking capacity is 10 kA Icn at 230/400 V AC per EN 60898, and under IEC 60947-2 it reaches 15 kA Icu at 400...415 V AC and 30 kA Icu at 230...240 V AC. The 4-pole configuration protects all three phases plus neutral, with suitability for isolation confirmed per IEC 60947-2. Occupies 8 modules of 9 mm pitch, so it takes 72 mm of rail width. Depth is 73 mm, height 81 mm. Certified to IEC 60947-2 and EN 60898 — the twin standards for industrial and residential MCBs.","metaTitle":"Schneider C60H4P6AD Miniature Circuit Breaker, D Curve, 6 A,","metaDescription":"Schneider Electric C60H4P6AD Multi9 MCB, 6 A rated, D curve, 4 poles, 10 kA breaking capacity at 230/400 V AC. IEC 60947-2 & EN 60898. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"IEC 60947-2 EN 60898","Curve code":"D","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"C60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Range of product":"C60","Breaking capacity":"10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2","Device short name":"C60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 2 N.m upside 2 N.m downside","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"6 A at 40 °C","Trip unit technology":"Thermal-magnetic","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"12...440 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/C60H4P6AD/miniature-circuit-breaker-c60h-4-poles-6-a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60H4P6AD/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60H4P6AD and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"What is the closest alternative to C60H4P6AD in the Multi9 family?","answer":"Within the same C60 range, the key variant is the C curve version (e.g., C60H4P6AC) which trips magnetically at 5 to 10 x In instead of the D curve's 10 to 14 x In. The D curve is the correct choice for motor and transformer loads with high inrush; the C curve suits general-purpose distribution. No pin-compatible alternative exists — the curve is the selection gate."},{"question":"What is C60H4P6AD's listed depth?","answer":"The depth is 73 mm, with a width of 72 mm (8 x 9 mm pitches) and height of 81 mm."},{"question":"What compliance documentation does this MCB carry?","answer":"Certified to IEC 60947-2 and EN 60898. Tropicalisation class 2 per IEC 60068-1. Suitability for isolation confirmed per IEC 60947-2. Operating and storage temperature ranges are specified per the standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60H4P6AD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60H4P6AD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}