{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60HC20R100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60HC20R100","canonicalUrl":"https://aoctrl.com/schneider/C60HC20R100","factsUrl":"https://aoctrl.com/api/mcp/products/C60HC20R100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H RCBO, 1 pole + N, 20 A, C curve, 100 mA earth leakage, 10 kA breaking capacity, thermal-magnetic trip, 50-250 V AC.","salesMarkdown":"The C60HC20R100 is a C60H-series RCBO (residual current circuit breaker with overcurrent protection) from Schneider Electric — 1 pole + N, rated 20 A at 30 °C, C-curve magnetic trip (5 to 10 × In), with 100 mA earth-leakage sensitivity (Class AC, instantaneous). It breaks up to 10 kA Icu at 50–250 V AC, 50/60 Hz, per IEC 1009-2-2. The C curve (5–10 × In) means the magnetic trip fires between 100 A and 200 A — designed for mixed resistive-inductive loads like small motor circuits, lighting banks, and control transformers where inrush is moderate but not as high as a D-curve would handle. The 100 mA earth-leakage threshold is for equipment protection, not personnel shock protection (that needs 30 mA or lower); it catches insulation faults before they escalate to a phase-to-ground short. Thermal-magnetic trip technology combines a bimetal strip for overload protection (time-delayed, inverse-time) and a solenoid for short-circuit protection (instantaneous above the magnetic threshold). The 20 A rating at 30 °C ambient means the thermal element tracks load current; derate for higher ambient temperatures per the manufacturer's curve. ## Deployment context The 1P+N format (switched phase, solid neutral) is typical for single-phase outgoing circuits in TN or TT earthing systems. Schneider Electric lists the C60HC20R100 as obsolete.","metaTitle":"C60HC20R100 C60H RCBO, 20 A C-Curve, 10 kA, Obsolete","metaDescription":"C60HC20R100 RCBO by Schneider Electric, 1P+N, 20 A, C curve, 100 mA earth leakage, 10 kA breaking capacity. Obsolete — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Standards":"IEC 1009-2-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3 conforming to EN 60898","Local signalling":"Positive break indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Right","Range of product":"C60","Breaking capacity":"10 kA Icu at 50...250 V AC 50/60 Hz conforming to IEC 1009","Device short name":"C60H RCBO","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Operating altitude":"2000 m","[In] rated current":"20 A at 30 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals (downstream) 10 mm² flexible Tunnel type terminals (downstream) 16 mm² rigid Tunnel type terminals (upstream) 16 mm² flexible Tunnel type terminals (upstream) 25 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"With","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Circuit breaker application":"Distribution","Earth-leakage protection class":"Class AC","[Ue] rated operational voltage":"50...250 V AC 50/60 Hz","Earth-leakage protection time delay":"Instantaneous"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/C60HC20R100/miniature-circuit-breaker-c60h-rcbo-1-pole-+-n-20-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60HC20R100/alternatives.json"},"ai":{"faq":[{"question":"What is C60HC20R100's listed standards (IEC 1009-2-2) on this component line?","answer":"The C60HC20R100 is designed and tested to IEC 1009-2-2, the standard for residual current operated circuit breakers with integral overcurrent protection (RCBOs)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60HC20R100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60HC20R100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}