{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60HC45R100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60HC45R100","canonicalUrl":"https://aoctrl.com/schneider/C60HC45R100","factsUrl":"https://aoctrl.com/api/mcp/products/C60HC45R100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H RCBO, 1 pole + neutral, 45 A, C curve, 100 mA earth leakage, 10 kA breaking capacity, obsolete.","salesMarkdown":"The C60HC45R100 is a C60H-series RCBO (residual current circuit breaker with overcurrent protection) from Schneider Electric, combining a 45 A thermal-magnetic MCB with 100 mA earth-leakage protection in a single 1P+N module. It snaps onto 35 mm symmetrical DIN rail and is rated for distribution outgoer circuits at 50...250 V AC, 50/60 Hz. The 10 kA Icu breaking capacity at 50...250 V AC conforms to IEC 1009 — sufficient for most sub-distribution boards where the upstream fault level is limited. Earth-leakage sensitivity is 100 mA, Class AC (instantaneous), meaning it detects sinusoidal residual currents only; not suitable for pulsating DC or variable-frequency drive circuits that generate smooth DC fault currents. Thermal-magnetic trip technology gives both overload (thermal bimetal) and short-circuit (solenoid) protection in one unit. The 20,000-cycle electrical durability is typical for a distribution RCBO — adequate for branch circuits with infrequent switching, not for motor-starting duty where higher endurance is needed. Schneider lists the C60HC45R100 as obsolete. If a form-fit-function replacement is needed, a parametric search for a 1P+N RCBO at 45 A, C-curve, 100 mA sensitivity, 10 kA breaking capacity, and DIN-rail mount will identify candidates; verify terminal capacity and neutral position (right) before substituting. The 1P+N module occupies two 9 mm pitches, so it fits a standard 18 mm width. Positive-break indication on the toggle gives visual confirmation of contact separation.","metaTitle":"C60HC45R100 C60H RCBO, 1P+N, 45A, C-curve, 100mA, obsolete","metaDescription":"C60HC45R100 RCBO, 1P+N, 45A, C-curve, 100mA earth leakage, 10kA breaking capacity. Obsolete — sourced to order against RFQ. IEC 1009-2-2, EN 60898.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Standards":"IEC 1009-2-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3 conforming to EN 60898","Local signalling":"Positive break indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Right","Range of product":"C60","Breaking capacity":"10 kA Icu at 50...250 V AC 50/60 Hz conforming to IEC 1009","Device short name":"C60H RCBO","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Operating altitude":"2000 m","[In] rated current":"45 A at 30 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals (downstream) 10 mm² flexible Tunnel type terminals (downstream) 16 mm² rigid Tunnel type terminals (upstream) 16 mm² flexible Tunnel type terminals (upstream) 25 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"With","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Circuit breaker application":"Distribution","Earth-leakage protection class":"Class AC","[Ue] rated operational voltage":"50...250 V AC 50/60 Hz","Earth-leakage protection time delay":"Instantaneous"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/C60HC45R100/miniature-circuit-breaker-c60h-rcbo-1-pole-+-n-45-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60HC45R100/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60HC45R100 and how do I get a price?","answer":"The C60HC45R100 is sourced to order through independent distribution against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What standards does the C60HC45R100 comply with?","answer":"The C60HC45R100 is designed to IEC 1009-2-2 (the RCBO product standard) and its limitation class 3 conforms to EN 60898."},{"question":"What is the C60HC45R100's curve code and what does it mean?","answer":"The C curve on this RCBO means the magnetic trip operates between 5 and 10 times the rated current (5...10 × In), suited for circuits with moderate inrush like lighting or small motors."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60HC45R100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60HC45R100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}