{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C60HC6R100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C60HC6R100","canonicalUrl":"https://aoctrl.com/schneider/C60HC6R100","factsUrl":"https://aoctrl.com/api/mcp/products/C60HC6R100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60H series RCBO, 1 pole + neutral, 6 A rated current, C-curve, 100 mA earth leakage, 10 kA breaking capacity, obsolete status.","salesMarkdown":"The C60HC6R100 is a C60H series residual current circuit breaker with overcurrent protection (RCBO), 1 pole + neutral, rated 6 A at 30 °C with a C-curve magnetic trip of 5...10 x In. It carries a 10 kA breaking capacity at 50...250 V AC 50/60 Hz per IEC 1009, and 100 mA earth leakage protection, Class AC, instantaneous. This is the outgoer protection for a distribution board — one module wide on 35 mm DIN rail, toggle actuated, with positive break indication on the handle. This part is marked obsolete by the manufacturer. The C-curve (5...10 x In) means magnetic trip between 30 A and 60 A — typical for inductive loads like small contactor coils or lighting ballasts where inrush exceeds a B-curve threshold. The 100 mA earth leakage sensitivity is Class AC (sinusoidal AC only), instantaneous — no time delay, so it trips on first fault. That sensitivity is common for general socket-outlet protection where 30 mA is too sensitive for the circuit leakage. Terminal capacity: 25 mm² rigid upstream, 16 mm² flexible downstream — enough for a 6 A circuit with some headroom for voltage drop. ## Integration Notes Mounts on 35 mm symmetrical DIN rail — one module width (roughly 9 mm pitch, 2 pitches total). Neutral is on the right. Tunnel terminals: torque to 2 N.m. Operating altitude limited to 2000 m; relative humidity 95 % at 55 °C, so it handles damp enclosure environments but not outdoor direct exposure.","metaTitle":"C60HC6R100 C60H RCBO, 6 A, C-Curve, 10 kA, Obsolete","metaDescription":"C60HC6R100 is an obsolete C60H RCBO, 1P+N, 6 A, C-curve, 100 mA earth leakage, 10 kA breaking capacity. Sourced to order against RFQ via independent channels.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Standards":"IEC 1009-2-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3 conforming to EN 60898","Local signalling":"Positive break indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Right","Range of product":"C60","Breaking capacity":"10 kA Icu at 50...250 V AC 50/60 Hz conforming to IEC 1009","Device short name":"C60H RCBO","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Operating altitude":"2000 m","[In] rated current":"6 A at 30 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals (downstream) 10 mm² flexible Tunnel type terminals (downstream) 16 mm² rigid Tunnel type terminals (upstream) 16 mm² flexible Tunnel type terminals (upstream) 25 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"With","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Circuit breaker application":"Distribution","Earth-leakage protection class":"Class AC","[Ue] rated operational voltage":"50...250 V AC 50/60 Hz","Earth-leakage protection time delay":"Instantaneous"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/C60HC6R100/miniature-circuit-breaker-c60h-rcbo-1-pole-+-n-6-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C60HC6R100/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C60HC6R100?","answer":"This obsolete part is sourced through independent distribution channels. Submit an RFQ for current availability and pricing; it is quoted to order, not held as live stock."},{"question":"What is the C60HC6R100's breaking capacity?","answer":"It is rated 10 kA Icu at 50...250 V AC 50/60 Hz conforming to IEC 1009."},{"question":"What standards does C60HC6R100 comply with?","answer":"It complies with IEC 1009-2-2 and is limitation class 3 conforming to EN 60898."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C60HC6R100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C60HC6R100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}