{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C6336M500","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C6336M500","canonicalUrl":"https://aoctrl.com/schneider/C6336M500","factsUrl":"https://aoctrl.com/api/mcp/products/C6336M500","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX400...630 series, MicroLogic 6.3 E-M electronic trip unit, 500 A at 65 °C, 3-pole, LSIG protection, LCD display, EN/IEC 60947-2.","salesMarkdown":"The Schneider Electric C6336M500 is a MicroLogic 6.3 E-M electronic trip unit for the ComPacT NSX400...630 range, rated 500 A at 65 °C. The 500 A rating at 65 °C means this trip unit is calibrated for continuous motor load at that current without derating at the elevated panel temperature; if your enclosure runs hotter, the ambient operating range extends to 70 °C, but you should verify the thermal curve against the motor's full-load amps. The LSIG scheme gives you adjustable long-time pickup from 250 to 500 A (Ir), short-time pickup adjustable across 9 settings from 5 to 13 x Ir, and ground-fault pickup also adjustable — so you can shape the curve to match motor inrush and coordination requirements. The trip unit is 3-pole (3P) with 3D protected poles, meaning all three poles are monitored and protected. The motor tripping classes available are 5, 10, 20, and 30, selectable via the trip unit settings, letting you match the overload curve to the motor's thermal withstand characteristics. ## Integration into the ComPacT NSX400...630 frame This trip unit mounts into a fixed-mount ComPacT NSX400...630 circuit breaker frame. The LCD display provides local readout of energy metering, protection settings, time-stamped events, demand values, and maintenance indicators. The communication capabilities include energy metering data, protection and alarm settings, time-stamped histories and event tables, instantaneous and demand values, maintenance indicators, demand current and power, power quality, and maximeters/minimeters — all accessible via the trip unit's communication port without additional modules. Zone selective interlocking (ZSI) is supported, which allows multiple downstream breakers to communicate trip signals for faster fault clearing while maintaining selectivity — useful in a motor control center with multiple feeders. Class II electrical shock protection means double insulation is provided, so no protective earth connection is required on the trip unit itself.","metaTitle":"Schneider Electric C6336M500 MicroLogic 6.3 E-M Trip Unit, 5","metaDescription":"Schneider Electric C6336M500 MicroLogic 6.3 E-M electronic trip unit, 500 A at 65 °C, LSIG protection, LCD display, EN/IEC 60947-2. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","title":"C6336M500","Standards":"EN/IEC 60947-2","description":"trip unit MicroLogic 6.3 EM for ComPacT NSX 630 circuit breakers, electronic, rating 500 A, 3 poles 3d","Display type":"LCD display","Network type":"AC","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 6.3 E-M","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection G : for ground fault protection","lifecycle_stage":"current","Local signalling":"Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point","Pollution degree":"3 conforming to IEC 60947-1","Range of product":"ComPacT NSX400...630","Trip unit rating":"500 A at 65 °C","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Motor","Type of measurement":"Energy meter","Motor tripping class":"5 10 30 20","Trip unit technology":"Electronic","Communication of data":"Energy metering Protection and alarm settings Time-stamped histories and event tables Instantaneous and demand values Maintenance indicators Demand current and power Power quality Maximeters/minimeters","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Electrical data recording":"Maintenance indicators","Product or component type":"Trip unit","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","Complementary motor protection":"Current unbalance Protracted starting time Stalled rotor Underload","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"With","Electrical shock protection class":"Class II","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","Long-time protection delay adjustment type tr":"Adjustable","Short-time protection delay adjustment type tsd":"Fixed","[Tr] Long-Time Protection Delay Adjustment Range":"120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20 720 s at 1.5 x Ir for trip class 30 38 s at 6 x Ir for trip class 30 30 s at 7.2 x Ir for trip class 30","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","Ground-fault protection pick-up adjustment type Ig":"Adjustable","[Ir] long-time protection pick-up adjustment range":"250...500 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"5...13 x Ir","Ground-fault protection time delay adjustment type tg":"Adjustable","[Ig] ground-fault protection pick-up adjustment range":"0.2...1 x In for In = 50 A Ig enable on/off","[Ii] instantaneous protection pick-up adjustment range":"6500 A","[Tg] Ground-Fault Protection Time Delay Adjustment Range":"0...0.4 s","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$460.61 – $1,311.49","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8b9276facbd968ca417c0891c4e0ecca.pdf","sourceUrl":"https://www.se.com/hk/en/product/C6336M500/trip-unit-micrologic-6-3-em-for-compact-nsx-630-circuit-breakers-electronic-rating-500-a-3-poles-3d/"},"ai":{"faq":[{"question":"What is C6336M500's listed range and standards?","answer":"It belongs to the ComPacT NSX400...630 range and complies with EN/IEC 60947-2 for low-voltage switchgear and controlgear."},{"question":"What protection functions does the MicroLogic 6.3 E-M provide?","answer":"It provides LSIG protection: long-time (L) overload, short-time (S) short-circuit with fixed delay, instantaneous (I) short-circuit, and ground-fault (G) protection. The long-time pickup is adjustable from 250 to 500 A, short-time pickup adjustable across 9 settings from 5 to 13 x Ir, and ground-fault pickup also adjustable."},{"question":"What motor protection features does this trip unit include?","answer":"Beyond the LSIG curve, it offers complementary motor protection: current unbalance, protracted starting time, stalled rotor, and underload. Motor tripping classes 5, 10, 20, and 30 are selectable."},{"question":"How do I get current pricing and availability for C6336M500?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What compliance documentation is available for C6336M500?","answer":"The trip unit is certified to EN/IEC 60947-2 and carries IP40 protection per IEC 60529. Pollution degree 3 per IEC 60947-1 and Class II electrical shock protection are specified. Specific RoHS, REACH, or UL documentation should be requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C6336M500","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C6336M500 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}